Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-27
[11]
"Add output of temperature range upper limit alarm": Set to "OFF".
[12]
"Temperature range lower limit alarm switching": Set to "OFF".
[13]
"Add output of temperature range lower limit alarm": Set to "OFF".
State (1): Start of operation "30 sec" elapsed, alarm notice as the bandwidth is not reached in
time.TEMP OUT signal ON.
State (2): Although it is within the bandwidth range, since the "stable time of TEMP READY" has not
elapsed, the alarm continues,TEMP OUT signal ON state continues.
Statu (3): Stable time "60 sec" elapsed, TEMP OUT signal OFF. READY signal ON.
State (4): Manual reset of alarm. Since the alarm cancellation condition is entered, the alarm OFF.
State (5): Although it is out of band width, READY signal continues as "READY is out of time".
State (6): Time when READY disappears after "30 sec" has elapsed, the READY signal OFF, alarm
report, TEMP OUT signal ON.
State (7): Manual reset of alarm. Since the alarm cancellation condition is not entered, the alarm ON
continues.
State (8): S
table time "60 sec" elapsed, TEMP OUT signal OFF. READY signal ON.
TEMP READY bandwidth lower limit
17.
Press the [▼] key. Displays TEMP READY bandwidth lower limit setting screen.
RUN
℃
READY
⇒
L
BAND
(
Alternately displayed
)
TEMP READY bandwidth lower limit
(
Setting range
:
-9.9 to -0.1
℃
)
Chiller
Operation
Stop
Circulating fluid
setting temperature 15.0 ° C
TEMP READY signal
ON
OFF
READY
Bandwidth
(upper limit) 17.0 ° C
READY
Bandwidth
(Lower limit) 13.0 ° C
60s
(3)
NOT TEMP READY
alarm
Generation
Without
Elapsed time
30s
30s
(1)
TEMP OUT signal
(When READY
output is set)
ON
OFF
Alarm manual reset
Alarm manual reset
60s
(2)
(4)
(5)
(6)
(7)
(8)
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......