HRX-OM-X084
Chapter 8
Control, Inspection, Exchange and Cleaning
8.3
Stop for a Long Time
HRR Series
8-12
5.
Loosen air releasing plug.Facility water will come out from facility water inlet port.
Fig. 8-6 Discharge of the facility water
6.
After draining the facility water, securely tighten the air release plug.
7.
Install the cover panel by reverse procedure. (Recommended tightening torque
:
1.5N
・
m)
Facility water outlet port
Air release
plug
Facility water inlet port