HRX-OM-X084
Chapter 5
Display and Setting of Various Functions
5.5 Advanced setting mode
HRR Series
5-22
MODE
Explanation
MODE1
Control the temperature so that the discharge temperature of
the circulating fluid is circulating fluid set tempe offset
temperature. Circulating fluid temperature indicates the
circulating fluid discharge temperature.
MODE2
Control the temperature so that the discharge temperature
of the circulating fluid is circulating fluid set temperature.
Circulating fluid temperature indicates the circulating fluid
discharge tempe offset temperature.
MODE3
Control the temperature so that the discharge temperature
of the circulating fluid is circulating fluid set tempe
offset temperature. Circulating fluid temperature indicates
the circulating fluid discharge temperature - offset
temperature.
OFF
Control the temperature so that the discharge temperature of
the circulating fluid is circulating fluid temperature set value.
■
Example of MODE 1
When the offset temperature is 1
o
C, the thermo-chiller controls the temperature at 31
o
C
(circulating fluid set tempe offset temperature.) Even if the discharge temperature is
31
o
C, the circulating fluid temperature is 30
o
C at the customer’s device because of 1
o
C of
heat radiation during sending of the fluid. Circualting fluid display temperature and
communication data is 31
o
C.
■
Example of MODE 2
When the offset temperature is -1
o
C, circulating fluid display temperature and the
communication data is 29
o
C (circulating fluid discharge tempe offset temperature),
and matches the circulating fluid temperature at the customer's device.
Circulating fluid display
temperature
31
℃
Circulating fluid set
temperature
30
℃
Offset temperature
1
℃
This produuct
Your system
Serial communication
Discharge
temperature 31
℃
30℃
Circulating fluid
temperature 31
℃
Heat
radiation
1
℃
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......