3.3 Installation
3-11
Preparation
1.
Prepare the cable and individual socket or earth leakagebreaker shown in the table
below.
2.
Strip the sheath from both ends of the cable.
3.
Disassemble the power supply connector (supplied as an accessory) and mount one
end of the cable to the L, N and E terminals and reassemble the power supply
connector.
4.
Connect the other end of the cable to crimped terminals that are connectable to the
power supply facility.
Fig 3-3
Cable connection
5.
Insert the power supply connector to the power supply connector socket.
6.
Connect the crimped terminals to the secondary side of the earth leakage breaker and
grounding on the power supply facility
Fig
3-4
Power supply connector connection
Cable
Qty. x size
3cores
×
14AWG
(
3cores
×
2.0mm2
)
*including ground
To customer facilities
crimped terminal
etc.
Power supply connector
N
E
(Earth)
L
Power supply connector
Earth leakage breaker
Power supply connector hole
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......