Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-37
Output of NOT TEMP READY
11.
Press the [▼] key. Displays screen for setting the output of the NOT TEMP READY
signal.
The user can select whether thre is an output signal when alarm "AL13 NOT TEMP READY"
occurs.
Set value
Contents
Initial value
ON
Output signal to contact output or serial
communication.
○
OFF
No signal is output.
―
【
Example
】
If the user does not want to generate an alarm, but wants a signal for contact output or serial
communication when alarm "AL13: NOT TEMP READY" occurs, it can be set as follows.
・
Chane NOT TEMP READY alarm
:
OFF
・
Output of NOT TEMP READY
signal
:
ON
Changing of circulating fluid temperature rise
12.
Press the [▼] key. Displays screen for changing the chiller behaviour when the
circulating fluid temperature rise
alarm occurs
.
The user can decide the chiller behavior if alarm "AL14 circulating fluid temperature rise"
occurs.
Set value
Contents
Initial value
OFF
Alarm is not generated.
○
WRN
Operation of this product will continue when the
alarm occurs.
―
FLT
Operation of this product will stop when the
alarm occurs.
―
RUN
RUN
No alarm is generated,
but a signal is output.
Output of NOT TEMP READY signal
TEMP
⇒
READY
⇒
OU
T
P
(
Alternately displayed
)
TEMP
⇒
OU
T
HI
⇒
ALARM
(
Alternately displayed
)
Operation at occurrence of circulating fluid
temperature rise alarm
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......