HRX-OM-X084
Chapter 9
Documents
9.1
Specifications
HRR Series
9-4
The cooling capacity will be reduced by 300W when option T1 [Inverter pump] is selected.
4: (1)Ambient temp.: 25
℃
, (2)Facility water temp: 25
℃
, (3)Circulating fluid temp.: 20
℃
, (4)Circulating fluid rated flow,
(5)Criculating fluid : Tap water,(6) Power supply :100V type:AC100V, 200V type :AC200V, (7)Piping length :
Shortest
5: Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly
connected.Installation environment and power supply are within specification range and stable.
6: The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20
℃
.
7: Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower
than the rated flow.
8: To be prepared by the customer. Use an earth 30mA/200V in power supply specification.
9: Front 1m/Height 1m/Static with no load. See note 4 for other conditions.
10: Dimension between panels. Projection is not included.
When option Y[With feet, and no Rack Mounting bracket] is selected, refer to [6.4.
Option Y
【
With feet and no
Rack Mounting bracket
】
].
11: Weight when the circulating fluid and facility water (for water-cooled type) is not included.
The weight will increase by 1kg when option DM [Electric conductivity c Applicable to deionized water
piping] is selected.
The weight will increase by 2kg when option T1 [Inverter pump] is selected.
12: Copper is not included when option M [Applicable to deionized water piping] is selected.
13: When option DM [Electric conductivity c Applicable to deionized water piping] is selected, these materials
are included.
14: Required flow rate when a load for the cooling capacity is applied at a condition of note 3.
15: If the altitude is 1000 m or more, please refer to "P.3-3 When Thermo-chiller installation in high altitude of 1000
meters or more".
16: No continuous voltage flucuation.
17: To be prepared by the customer.
18: (1)Ambient temp: 25
℃
, (2)Circulating fluid temp: 20
℃
, (3) Circulating fluid rated flow, (4) Circulating fluid : Tap
water, (5) Power supply :100V type:AC100V, 200V type :AC200V, (6)Piping length: Shortest,
(7)Rated cooling load is applied.
19: When Option DM [Electric conductivity c Applicable to deionized water piping] is selected, DI filter will be
added.
Piping thread type : When F is selected, G thread adapter set will be added.
Piping thread type : When N is selected, NPT thread adapter set will be added.
Not included for options Z and Z1.
20: Not included for options Z is selected.
21
Not included for options Z,Z1 is selected.
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......