- 57 -
No.EX##-OML0007
Analog input unit parameters
Setting method
No
Parameter
(EDS
parameter)
Setting value
Contents
Setting
level
Default
setting By PLC By HT
Enable
Enable sensor power supply
short circuit detection
O
1
Short circuit
detection
(Monitor
short circuit)
Disable
Disable sensor power supply
short circuit detection
Unit
O O
2
Analogue
input range
(Ch # range)
0~10 V, 1~5 V, 0~5 V,
-10~+10 V, -5~+5 V,
0~20 mA, 4~20 mA,
-20~+20 mA
Select analogue input range
Channel
-10 ~
+10 V
O O
3
Analogue
data format
(Data
format)
Offset Binary, Sign &
Magnitude, 2s
complement
Select analogue data format
Unit
Offset
binary
O O
4
Analogue
filter
(Ch # filter)
None,
2 value average,
4 value average,
8 value average
Select analogue data filter
Unit
2 value
average
O O
Enable
If the analogue input exceeds
the maximum allowable input
range (0.5 %), a diagnostic
error will be generated
5
Over range
detection
(Monitor
over range)
Disable
Above diagnostic error will not
be generated.
Unit Enable O
O
Enable
If the analogue input exceeds
the minimum allowable input
range (0.5 %), a diagnostic
error will be generated
6
Under range
detection
(Monitor
under range)
Disable
Above diagnostic error will not
be generated.
Unit Enable O
O
7 Enable
If the analogue input exceeds
the upper user set lower limit,
diagnostic error will be
generated
Disable
Above diagnostic error will not
be generated.
Disable
User set
value upper
limit error
(Analogue
upper limit)
Val
User set value is settable
according to the table below
Channel
10 V
Note)
X O
8 Enable
If the analogue input falls
below the lower user set lower
limit, diagnostic error will be
generated
Disable
Above diagnostic error will not
be generated.
Disable
User set
value lower
limit error
(Analogue
under limit)
Val
User set value is settable
according to the table below.
Channel
10 V
Note)
X O
Note) Factory default setting for analogue input range is –10 ~ +10 V
When changing the analogue input measurement range, confirm the set value and set the correct
value accordingly.