![SMC Networks EX600-AX Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/smc-networks/ex600-ax/ex600-ax_operation-manual_1299349068.webp)
- 68 -
No.EX##-OML0007
System object (66h)
Instance attribute
Attribute
ID
Access Name Type
Description / Value
105 Get
System
status
1
UINT
Bit 0: Power supply voltage monitor for output
Bit 1: Power supply voltage monitor for control and input
Bit 2: (reserved)
Bit 3: Unit disconnected
Bit 4: Connection error
Bit 5: Configuration memory error
Bit 6: System error
Bit 7: Hardware error
Bit 8: Analogue value falls below user setting lower value
Bit 9: Analogue value exceeds user setting upper value
Bit 10: Analogue value falls below measurement range lower value
Bit 11: Analogue value exceeds measurement range upper value
Bit 12: ON/OFF counter exceeded
Bit 13: Open circuit detection
Bit 14: Short circuit detected (at output)
Bit 15: Short circuit detected (at input)
106 Get
System
status
2
UINT
Bit 0: Digital input fault
Bit 1: Digital output fault
Bit 2: Analog input fault
Bit 3: (reserved)
Bit 4: SI unit fault
Bit 5: (reserved)
Bit 6: (reserved)
Bit 7: (reserved)
Bit 8: (reserved)
Bit 9: (reserved)
Bit 10: (reserved)
Bit 11: (reserved)
Bit 12: (reserved)
Bit 13: (reserved)
Bit 14: (reserved)
Bit 15: (reserved)