HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 20 of 34
Num
Parameter
Range
Default
Remark
P 25
(P20)
Over speed
shutdown
(0-6000)RPM
1710
When the engine speed is
over than the point and hold
great
than
2
seconds,
genset
over
shutdown
speed is active.
P 26
(P21)
Gens
under
freq
shutdown
(0-75.0)Hz
45.0
When genset frequency is
low than the point, genset
low frequency shutdown
and hold great than 10
seconds is active.
P 27
(P22)
Gens
over
freq
shutdown
(0-75.0)Hz
57.0
When genset frequency is
over than the point and hold
great
than
2
seconds,
genset
over
shutdown
frequency is active.
P 28
(P23)
High
temperature
shutdown
(80-140)°C
98
When engine temperature
sensor value is large than
this point and remain for 2
seconds,
send
out
shutdown alarm. When the
value is 140, send out
warning alarm.
(It‟s suited
for
engine
temperature
sensor only).
P 29
(P24)
Low
oil
pressure
shutdown
(0-400)kPa
103
When engine oil pressure
sensor value is less than
this point and remain for 2
seconds,
send
out
shutdown alarm. When the
value is zero, send out
warning alarm. (I
t‟s suited
for oil pressure sensor
only).
P 30
(P25)
Low Fuel level (0-100)%
10
When low Fuel level sensor
value is less than this point
and remain for 10 seconds,
send out warning alarm.
P 31
(P26)
Lose
speed
delay
(0-20.0)s
5.0
When speed is zero and
remain for the delay, send
out shutdown alarm. When
the delay is zero, send out
warning alarm.