HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 26 of 34
7.3 DIGIT INPUT 1-5 TABLE (TABLE 3)
Num
Content
Description
0
Not used
1
High Temp. input
After the end of the delay in the safe operation,
if the signal is active, genset will immediately
alarm shutdown.
2
Low OP alarm input
3
Auxiliary warn input
Auxiliary warn alarm digital input.
4
Auxiliary shutdown
alarm input
When power on, if active, genset will shut down
immediately.
5
Stop after cooled
During engine running, if the engine occur high
temperature shutdown, when the input is active,
the engine will first initiate cooling delay and
then stop, else will stop immediately.
6
Gens closed input
The input state of genset closed.
7
Mains closed input
The input state of Mains closed.
8
Inhibit WTH STOP
When it is active, during engine running, if the
engine appears high temperature, the engine
will only send out high temperature warning
alarm, not stop.
9
Inhibit OPL STOP
When it is active, during engine running, if the
engine appears low oil pressure, the engine will
only send out low oil pressure warning alarm,
not stop.
10
Remote start input
In automatic state, controller remote starts the
signal effectively when starting.
7.4 SENSOR (TABLE 4)
Num
Content
Remark
1
Temperature
Sensor
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4SGD(DongKang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
Defined
input
resistance
range
is
0-999.9 ohm, factory
default is SGX
2
Pressure
Sensor
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(DongKang sensor)
Defined
input
resistance
range
is
0-999.9 ohm, factory
default is SGX