HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 24 of 34
Num
Parameter
Range
Default
Remark
P 67
(P62)
Freq
disconnect
(10-30)Hz
14
When genset frequency is
large than this point, starter
will disconnect.
P 68
(P63)
OP disconnect (0-400)kPa
200
When engine oil pressure is
large than this point, starter
will disconnect.
P 69
(P64)
Select AC
system
0 3P 4L
1 2P 3L
2 1P 2L
0
3P4L(3 phase 4 wire)
P70
(P65)
Select temp.
sensor
(0-8)
08
SGX
P71
(P66)
Select press
sensor
(0-8)
08
SGX
P72
(P67)
Select liquid
level sensor
(0-5)
03
SGD
P73
(P68)
Temperature
sensor
custom curve
setting
Need to set up eight first
acts of the current data set
the number of items, the
second act to set the
resistance value of the third
act to set the resistance
value of the temperature
corresponding to the value
of.
P74
(P69)
Oil pressure
sensor
custom curve
setting
Need to set up eight first
acts of the current data set
the number of items, the
second act to set the
resistance value, the third
act to set the resistance
value
of
the
pressure
corresponding to the value
of.
P75
(P70)
Liquid level
sensor
custom curve
setting
Need to set up eight first
acts of the current data set
the number of items, the
second act to set the
resistance value, the third
act to set the resistance
value of the value of the
corresponding level.