HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 16 of 34
Pin
Function
Dim
Description
15
Magnetic pickup
+ve
Connect to Magnetic Pickup device
16
Magnetic pickup
-ve
17
Temp.
sensor
input
Connecting
water/cylinder
temperature resistance type
sensor.
Reference
table 4
18 Oil pressure input
Connect
to
oil
pressure
sensor.
19 Liquid level input
Connect to liquid level sensor.
20 Auxiliary input 1
1.0mm Switch to -ve
Reference
table 3
21 Auxiliary input 2
1.0mm Switch to -ve
22 Remote start input 1.0mm Switch to -ve
23
CT secondary for
A
1.5mm
Connect to secondary of A monitoring
CT
24
CT secondary for
B
1.5mm
Connect to secondary of B monitoring
CT
25
CT secondary for
C
1.5mm
Connect to secondary of C monitoring
CT.
26
CT
secondary
common
1.5mm See also back install instructions.
27
Gens A voltage
monitoring
1.0mm
Connect to Genset A output
(Recommend 2A fuse)
28
Gens B voltage
monitoring
1.0mm
Connect to Genset B output
(Recommend 2A fuse)
29
Gens C voltage
monitoring
1.0mm
Connect to Genset C output
(Recommend 2A fuse)
30 Gens neutral input 1.0mm Connect to Genset neutral terminal.
31
Mains A voltage
monitoring
1.0mm
Connect to mains A output.
(Recommend 2A fuse)
32
Mains B voltage
monitoring
1.0mm
Connect to mains B output.
(Recommend 2A fuse)
33
Mains C voltage
monitoring
1.0mm
Connect to mains C output.
(Recommend 2A fuse)
34
Mains neutral
input
1.0mm Connect to mains neutral terminal.
35
RS485 port
common GND
0.5mm
Use only
120Ω RS485 approved cable.
36 RS485 port A(-)
0.5mm
37 RS485 port B(+)
0.5mm
38 Auxiliary input 4
1.0mm Switch to -ve
39 Auxiliary input 5
1.0mm Switch to -ve