HAT828 High Speed ATS Controller User Manual Page 51 of 56
No.
Items
Description
Remark
38
AUX. INPUT 8
Digital Intput 8
Default: Not Used.
Ground (B-) connected is active.
39
AUX. OUTPUT 5
Aux. Output Port 5
Default: Not Used.
Volts free relay; Normally Open
output. Capacity: 10A AC250V.
40
41
AUX. OUTPUT 6
Aux. Output Port 6
Default: Not Used.
Volts free relay; Normally Open
output. Capacity: 10A AC250V.
42
43
AUX. OUTPUT 7
Aux. Output Port 7
Default: Not Used.
Volts free relay; Normally Open
output. Capacity: 10A AC250V.
44
45
AUX. OUTPUT 8
Aux. Output Port 8
Default: Not Used.
Volts free relay; Normally Open
output. Capacity: 10A AC250V.
46
47
AUX. OUTPUT 9
COM
Aux. Output Port
9
Default: Genset Start, Normally Close
Output.
Volts free relay; Normally Open/Close
output. Capacity: 8A AC250V.
48
N/C
49
N/O
50
AUX. OUTPUT 10
COM
Aux. Output Port
10
Default: Not Used.
Volts free relay; Normally Open/Close
output. Capacity: 8A AC250V.
51
N/C
52
N/O
53
RS485-2 B(-)
RS485-2
Communication
Port
120Ω impedance matched resistance
should be connected according to the
different situation.
54
RS485-2 A(+)
55
PE
Ground Terminal
56
RS485-1 B(-)
RS485-1
Communication
Port
120Ω impedance matched resistance
should be connected according to the
different situation.
57
RS485-1 A(+)
USB
USB
D-type USB Communication
Port
Parameters setting and software
upgrading via PC