HAT828 High Speed ATS Controller User Manual Page 35 of 56
No.
Item
Description
23
Forced Manual Mode
Set the controller in Manual mode compulsively.
24
Forced Auto Mode
Set the controller in Auto mode compulsively.
25
Panel Lock
Panel key operations are inhibited (Except Up, Down, Confirm, Return
and Lamp Test keys).
26
Reserved
27
Scheduled Start/Stop
Inhibit
Schedule Start and Stop function are deactivated.
28
Simulate S1 OK
Simulate S1 voltage is normal; the S1 voltage abnormal delay is
deactivated.
29
Simulate S2 OK
Simulate S2 voltage is normal; the S2 voltage abnormal delay is
deactivated.
30
Auto Transfer/Restore
Input
Auto trans. auto restore when active and auto trans. non-restore
when inactive.
31
Reserved
32
Reserved
33
Remote Control Inhibit Remote control operation is inactive when input is active.
34
Reserved
35
Reserved
8.3.2
OUTPUT PORTS FUNCTION DESCRIPTION
Table 18 – Output Ports Function Description
No.
Items
Description
0
Not Used
Output port is invalid.
1
Custom Combined 1
2
Custom Combined 2
3
Custom Combined 3
4
Custom Combined 4
5
Custom Combined 5
6
Custom Combined 6
7
Reserved
8
Reserved
9
Reserved
10
Reserved
11
Common Alarm
It includes fault alarm and warn alarm.
12
Common Fault Alarm
It includes “Transfer Failure” alarm.
13
Common Warn Alarm
It includes “Battery Over/Under Voltage” warning.