HAT828 High Speed ATS Controller User Manual Page 23 of 56
No.
Item
Range
Default
Description
13
Set Value
(0~200)%
120
Upper limit value of voltage; it is
abnormal if the value has exceeded the
set value.
14
Return Value
(0~200)%
115
Upper limit return value of voltage; it is
normal only when the value has fallen
below the set value.
15
Under voltage Warn (0~1)
1
0: Disable 1: Enable
16
Set Value
(0~200)%
80
Lower limit value of voltage; it is
abnormal if the value has fallen below
the set value.
17
Return Value
(0~200)%
85
Lower limit return value of voltage; it is
normal only when the value has
exceeded the set value.
18
Rated Frequency
(10.0~75.0)Hz 50.0
Rated frequency of AC system.
19
Over Frequency
Warn
(0~1)
1
0: Disable 1: Enable
20
Set Value
(0~200)%
110
Upper limit value of frequency; it is
abnormal if the value has exceeded the
set value.
21
Return Value
(0~200)%
104
Upper limit return value of frequency; it
is normal only when the value has fallen
below the set value.
22
Under Frequency
Warn
(0~1)
1
0: Disable 1: Enable
23
Set Value
(0~200)%
90
Lower limit value of frequency; it is
abnormal if the value has fallen below
the set value.
24
Return Value
(0~200)%
96
Lower limit return value of frequency; it
is normal only when the value has
exceeded the set value.
25
Reverse Phase Seq. (0~1)
1
0: Disable 1: Enable
26
Instant. Under Volt
(0~1)
1
0: Disable 1: Enable
27
Set Value
(0~100)%
20
The power supply is judged to be off
when the instantaneous under voltage is
less than this value. The quick switch
function is enabled in Auto Mode.