FP302 - Operation, Maintenance and Instructions Manual
3.14
Temperature Calibration
The CAL_TEMPERATURE parameter may be used to adjust the temperature sensor located on the
converter body to improve the temperature measuring accuracy. The temperature range covers
from –40 °C to +85 °C. The SECONDARY_VALUE parameter shows value of this measurement.
Figure 3.11 – How to Calibrate the Temperature Sensor
Display Transducer Block
The local adjustment tree is entirely configured by the Syscon. This means that the user can select
the best option for his application. The Transducer block is factory-configured with options to adjust
UPPER and LOWER Trim, to monitor the input transducer and to check the tag. Normally, the
FP302 is better configured by the Syscon, but the LCD local functionality allows for easy and quick
action on given parameters, since it does not depend on the network communication and
connections. Among the possibilities of local adjustment, the following options are emphasized:
mode block, outputs monitoring, tag visualization and adjustment of tuning parameters.
The user interface is described in the item on Programation using the local adjustment. It shows in
detail the resources of the transducer display. All Smar series 302 field devices have the same
operational methodology.Therefore, after using it at the first time, the user will be able to deal with
all of them.
All function blocks defined by Foundation Fieldbus™ have a description of their characteristics
written on binary files by the Device Description Language. This feature enables third party
configurators under the Device Description Service to interpret them and make them ready for
configuration. The serie 302 function blocks and transducers were strictly defined to comply with the
Foundation Fieldbus™ specifications in order to be interoperable with other parts.
To enable the local adjustment using the magnetic screwdriver you must previously prepare the
parameter related to the operation via the Syscon. Figures 3.8 and 3.9 show all parameters and
their respective values to be configured according to the local adjustment with the magnetic tool. All
figures shown on the display are default values.
Содержание FP302
Страница 1: ...ION FP302 F P 3 0 2 M E ...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK ...
Страница 8: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK ...
Страница 13: ...Installation 1 5 Network Configuration and Topology Figure 1 4 Bus Topology Figure 1 5 Tree Topology ...
Страница 18: ...FP302 Operation Maintenance and Instructions Manual 2 4 ...
Страница 37: ...Configuration 3 19 Figure 3 18 Step 1 Figure 3 19 Step 2 Figure 3 20 Step 3 ...
Страница 40: ...FP302 Operation Maintenance and Instructions Manual 3 22 ...
Страница 46: ...FP302 Operation Maintenance and Instructions Manual 4 6 Exploded View Figure 4 7 Exploded View ...
Страница 50: ...FP302 Operation Maintenance and Instructions Manual 4 10 ...
Страница 54: ...FP302 Operation Maintenance and Instructions Manual 5 4 ...
Страница 60: ... Crrgpfkz C C08 FM Approvals Factory Mutual ...
Страница 61: ... Crrgpfkz C C09 Canadian Standards Association CSA ...
Страница 62: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 ...