Figure 3.1 – How to choose the Calibration engineering unit
The lower value will be used as an example:
Write 3 psi or the lower value on the CAL_POINT_LO parameter. The trim procedure will initialize.
Figure 3.2 – Lower Point Calibration
Check the readout on the pressure meter and write the value on the FEEDBACK_CAL parameter.
Keep writing until reading 3.0 psi or the lower value on the pressure meter.