Installation
1.3
Electric Connection
To access the terminal block, remove the Electric Connection cover. This cover can be locked with
its locking screw. To release it, rotate the locking screw clockwise.
Figure 1.1
- Cover Locking Screw
The access of signal cables and their connection to the terminals are done through one of the two
orifices in the electronic housing, by linking them to a electric conduit o cable clamp. The conduit
threads must be sealed according to the required method. The unused orifice must be sealed with a
plug or sealant.
The electrical orifices must be connected in a way that prevents humidity inside the device. After
completing the connections, shut the device cover to avoid humidity.
The terminal block has screws to receive fork or eye terminals.
Figure 1.2 – Electric Connections
NOTE
The unused cable entries should be plugged and sealed accordingly to avoid humidity entering, which can
cause the loss of the product’s warranty.
Содержание FP302
Страница 1: ...ION FP302 F P 3 0 2 M E ...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK ...
Страница 8: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK ...
Страница 13: ...Installation 1 5 Network Configuration and Topology Figure 1 4 Bus Topology Figure 1 5 Tree Topology ...
Страница 18: ...FP302 Operation Maintenance and Instructions Manual 2 4 ...
Страница 37: ...Configuration 3 19 Figure 3 18 Step 1 Figure 3 19 Step 2 Figure 3 20 Step 3 ...
Страница 40: ...FP302 Operation Maintenance and Instructions Manual 3 22 ...
Страница 46: ...FP302 Operation Maintenance and Instructions Manual 4 6 Exploded View Figure 4 7 Exploded View ...
Страница 50: ...FP302 Operation Maintenance and Instructions Manual 4 10 ...
Страница 54: ...FP302 Operation Maintenance and Instructions Manual 5 4 ...
Страница 60: ... Crrgpfkz C C08 FM Approvals Factory Mutual ...
Страница 61: ... Crrgpfkz C C09 Canadian Standards Association CSA ...
Страница 62: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 ...