Configuration
3.5
Idx
Parameter
Type
Range
Valid
Initial
Value
Unit
Memory
Description
hardware or software on the
Transducer
7
UPDATE_EVT
DS-73
-
-
Na
D
Alert for any static data.
8
BLOCK_ALM DS-72
-
-
Na
D
Parameter used for configuration,
hardware or other failures.
9
TRANSDUCER_DIRECTORY
Array of
Unsigned16
-
- None N
Selection of several Transducer
Blocks.
10
TRANSDUCER_TYPE
Unsigned16
-
Other
None
N
Type of Transducer per class
11
XD_ERROR Unsigned8
-
Default value
set
None D
Calibration status.
12
COLLECTION_DIRECTORY
Array of
Unsigned 32
- -
None
S
Transducer index number on the
Transducer Block
13
FINAL_VALUE
DS-65
-
-
FRV
D
AO block desired pressure and
status
14
FINAL_VALUE_RANGE
DS-68
-
-
FRV
S
Upper and lower values,
engineering units and number
of decimal places to be used on
FINAL_VALUE
15
CAL_POINT_HI
Float
12-32 psi
30
CU
S
Upper Calibration Value
16
CAL_POINT_LO
Float
2.5-5 psi
3
CU
S
Lower Calibration Value
17
CAL_MIN_SPAN Float
-
7
CU
S
Minimum allowed span value. This
information is needed so that both
upper and lower calibration points
are not too close after calibrating.
18
CAL_UNIT Unsigned16
-
Psi
E
S
Engineering unit of the Equipment
description for the calibration
values.
19
CONV_SN
Unsigned32
-
-
None
S
Converter serial number
20
CAL_METHOD Unsigned8
-
Factory
None
S
Method used on last sensor
calibration.
21
ACT_FAIL_ACTION Unsigned8
-
-
None
S
Specifies the actuator action in
case of failure.
22
ACT_MAN_ID Unsigned32
-
-
None
N
Actuator manufacturer
Identification number.
23 ACT_MODEL_NUM
VisibleString
-
NULL
None
N
Actuator model number
24
ACT_SN
VisibleString
-
-
None
N
Actuator serial number.
25
VALVE_MAN_ID Unsigned32
-
-
E
N
Valve manufacturer identification
number.
26
VALVE_MODEL_NUM
VisibleString
-
NULL
None
N
Valve model number.
27
VALVE_SN
VisibleString
-
-
None
N
Valve serial number.
28 VALVE_TYPE
Unsigned8
-
-
E
N
Valve
type
29
XD_CAL_LOC VisibleString
-
NULL
None
S
Place of last equipment
calibration.
30
XD_CAL_DATE
Time of Day
-
-
None
S
Date of last equipment calibration
31
XD_CAL_WHO VisibleString
-
NULL
None
S
Name of last person who made
the Calibration.
32
SECONDARY_VALUE DS-65
-
-
SVU
D
Secondary value related to the
temperature sensor.
33
SECONDARY_VALUE_UNIT
Unsigned16
-
°
C
E
S
SECONDARY_VALUE
engineering unit parameter
34
SENSOR_RANGE
DS-68
-
3-30 psi
FRV
S
Pressure sensor upper and
lower value, engineering unit
and number of decimal points.
35
BACKUP_RESTORE Unsigned8
See table
None None S
Parameter for backup or to
recover configuration data.
36 COEFF_PRESS_POL0
Float
±
INF
-
None
S
Pressure Zero coefficient.
37 COEFF_PRESS_POL1
Float
±
INF
-
None
S
Pressure 1 coefficient..
38 COEFF_PRESS_POL2
Float
±
INF
-
None
S
Pressure 2 coefficient..
39 COEFF_PRESS_POL3
Float
±
INF
-
None
S
Pressure 3 coefficient.
40 COEFF_PRESS_POL4
Float
±
INF
-
None
S
Pressure 4 coefficient
41
COEFF_PRESS_POL5 Float
±
INF
-
None
S
Pressure 5 coefficient..
42 COEFF_PRESS_POL6
Float
±
INF
-
None
S
Pressure 6 coefficient.
43 COEFF_PRESS_POL7
Float
±
INF
-
None
S
Pressure 7 coefficient.
Содержание FP302
Страница 1: ...ION FP302 F P 3 0 2 M E ...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK ...
Страница 8: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK ...
Страница 13: ...Installation 1 5 Network Configuration and Topology Figure 1 4 Bus Topology Figure 1 5 Tree Topology ...
Страница 18: ...FP302 Operation Maintenance and Instructions Manual 2 4 ...
Страница 37: ...Configuration 3 19 Figure 3 18 Step 1 Figure 3 19 Step 2 Figure 3 20 Step 3 ...
Страница 40: ...FP302 Operation Maintenance and Instructions Manual 3 22 ...
Страница 46: ...FP302 Operation Maintenance and Instructions Manual 4 6 Exploded View Figure 4 7 Exploded View ...
Страница 50: ...FP302 Operation Maintenance and Instructions Manual 4 10 ...
Страница 54: ...FP302 Operation Maintenance and Instructions Manual 5 4 ...
Страница 60: ... Crrgpfkz C C08 FM Approvals Factory Mutual ...
Страница 61: ... Crrgpfkz C C09 Canadian Standards Association CSA ...
Страница 62: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 ...