Section 5
5.1
TECHNICAL CHARACTERISTICS
Functional Specifications
Output Signal
Standard: 3 – 15 psi (0.2 – 1.0 Kgf/cm²);
Extended: 3 – 30 psi (0.2 – 2.0 Kgf/cm²).
Input Signal
Digital only, Fieldbus, voltage mode 31.25 Kbit/s bus powered.
Power Source
Bus powered: 9-32 Vdc;
Quiescent Consumption Current: 12 mA;
Output Impedance @7.8 KHz to 39 KHz:
−
Without Intrinsic Safety: > 3 k
Ω
;
−
With Intrinsic Safety: > 400 k
Ω
; (in the assumption of a S.I. intrinsic bus on the power source).
Air Supply
18 -100 psi (1.24 – 7 Kgf/cm²) – free from oil, dirt and water.
Indication
Digital indicator (LCD) with 4½ numerical digits.
Classified Area Certification
According to ordering code.
Temperature Limits
Ambiente:
-40
to
85 °C
-40
to
185 °F
Storage:
-40
to
90 °C
-40
to
194 °F
Process:
-10
to
60 °C
-14
to
140 °F
Digital Display:
-40
to
85 °C
-40
to
185 °F Without damage.
Humidity Limits
0 to 100% Relative Humidity.
Connecting Time
Approximately 10 sec.
Update Time
Approximately 0.5 sec.
Configuration
Via the local adjustment and System302-7 or other FF (F
OUNDATION
™
fieldbus) configurator.
Performance Specifications
Precision
0.4% of Spam; includes hysterisis and stability effects.
Air Consumption
0.30 Nm³/h (0.18 scfm) for 1.24 bar (18 psi) supply;
0.45 Nm³/h (0.26 scfm) for 2.8 bar (40 psi) supply;
0.80 Nm³/h (0.47 scfm) for 7 bar (100 psi) supply.
Maximum Air Flow Capacity
3.40 Nm³/h (2 scfm) for 1.24 bar (18 psi) supply;
6.80 Nm³/h (4 scfm) for 2.8 bar (40 psi) supply;
15.30 Nm³/h (9 scfm) for 7 bar (100 psi) supply.
Содержание FP302
Страница 1: ...ION FP302 F P 3 0 2 M E ...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK ...
Страница 8: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK ...
Страница 13: ...Installation 1 5 Network Configuration and Topology Figure 1 4 Bus Topology Figure 1 5 Tree Topology ...
Страница 18: ...FP302 Operation Maintenance and Instructions Manual 2 4 ...
Страница 37: ...Configuration 3 19 Figure 3 18 Step 1 Figure 3 19 Step 2 Figure 3 20 Step 3 ...
Страница 40: ...FP302 Operation Maintenance and Instructions Manual 3 22 ...
Страница 46: ...FP302 Operation Maintenance and Instructions Manual 4 6 Exploded View Figure 4 7 Exploded View ...
Страница 50: ...FP302 Operation Maintenance and Instructions Manual 4 10 ...
Страница 54: ...FP302 Operation Maintenance and Instructions Manual 5 4 ...
Страница 60: ... Crrgpfkz C C08 FM Approvals Factory Mutual ...
Страница 61: ... Crrgpfkz C C09 Canadian Standards Association CSA ...
Страница 62: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 ...