Configuration
3.11
Figure 3.7 – Pressure Trim
Choose the unit to be used on the XD_SCALE parameter for the analog output block observing the
sensor 100% and 0% limits.
Also, on every calibration save the trim data on the CAL_POINT_LO_BACKUP and
CAL_POINT_HI_BACKUP parameters, through the BACKUP_RESTORE parameter, using the
LAST_TRIM_BACKUP option.
Via Local Adjustment
To enter the local adjustment mode, insert the magnetic screwdriver in orifice “Z” until the “MD”
readout appears in the display. Remove the magnetic tool and put it in orifice “S”. Remove and re-
insert the magnetic tool in “S” until the “Loc Adj” message appears. The message will be displayed
for 5 seconds after removing the tool. Insert the magnetic screwdriver in “Z” to access the local
adjustment and the monitoring tree.
Move to the “LOWER” parameter. To start the calibration, activate the “LOWER” parameter by
inserting a magnetic screwdriver in orifice “S”, and enter the value 3.0 psi or inferior. When removing
the magnetic tool from “S”, the output will be adjusted with a value close to the desired one. The
user must “sweep” the tree up to the FEEDBACK_CAL parameter and activate it by inserting the
magnetic screwdriver in “S” to reach the reference pressure value.
Continue writing on this parameter until reading 3.0 psi or the lower pressure value.
Move to the “UPPER” parameter. To start the calibration actuate on this parameter by inserting the
magnetic screwdriver in “S”.
It is possible to enter 30.0 psi or the wanted value wanted. When removing the magnetic
screwdriver from “S”, the output will be adjusted with a value close to the desired one. The user
must “sweep” the tree up to the FEEDBACK_CAL parameter and activate it by inserting the
magnetic screwdriver in “S” to reach the value obtained from the reference pressure.
The user should continue writing on this parameter until reading 30.0 psi.
NOTE
Exiting the Trim mode via the local adjustment is automatically done, if the magnetic screwdriver is not used for
approximately 16 seconds.
Содержание FP302
Страница 1: ...ION FP302 F P 3 0 2 M E ...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK ...
Страница 8: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK ...
Страница 13: ...Installation 1 5 Network Configuration and Topology Figure 1 4 Bus Topology Figure 1 5 Tree Topology ...
Страница 18: ...FP302 Operation Maintenance and Instructions Manual 2 4 ...
Страница 37: ...Configuration 3 19 Figure 3 18 Step 1 Figure 3 19 Step 2 Figure 3 20 Step 3 ...
Страница 40: ...FP302 Operation Maintenance and Instructions Manual 3 22 ...
Страница 46: ...FP302 Operation Maintenance and Instructions Manual 4 6 Exploded View Figure 4 7 Exploded View ...
Страница 50: ...FP302 Operation Maintenance and Instructions Manual 4 10 ...
Страница 54: ...FP302 Operation Maintenance and Instructions Manual 5 4 ...
Страница 60: ... Crrgpfkz C C08 FM Approvals Factory Mutual ...
Страница 61: ... Crrgpfkz C C09 Canadian Standards Association CSA ...
Страница 62: ...HR524 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 ...