General Information
User Manual
WB1100LV-11:FE2606
Page 59
I-Ni-Test
Impulse setting for impedance monitoring. This parameter only
takes effect when the Windy Boy is deactivated (disconnected
on the AC side) or in "Stop" mode.
Inst.-Code
Parameters for stand-alone grid recognition can only be
changed after entering the SMA grid guard password.
LDVtgC
Compensation for the voltage drop in the cabling.
With this parameter, the voltage drop between the inverter and
the grid connection point is taken into account. The 10-minute
average voltage at the inverter connection must not exceed the
sum of ACVtgRPro plus LDVtgC. The parameter LDVtgC is preset
to 0 V for Germany. The parameter LDVtgC is preset to 50 V for
grid areas in which the additional surge voltage protection is not
required (see parameter ACVtgRPro). Thus, the surge voltage
protection is deactivated for these grid areas (253 V + 50 V =
303 V) and only the fast cut-off via the Uac-Max parameter
intervenes.
Plimit
Upper limit for AC output power.
Pmax
Reduces the Windy Boy's maximum output power to adapt to
wind turbines with lower output power.
P-Wind-Mid
Defines the power threshold, after which the curve climbs more
steeply.
P-Wind-Ramp
Controls a delayed startup of the characteristic curve, only after
the Windy Boy has been switched on. This prevents the
generator from being suddenly presented with a heavy load.
SMA-SN
Serial number of the Windy Boy
Software-BFR
Firmware version of the operation control unit (BFR).
Software-SRR
Firmware version of the current control unit (SRR).
Speicherfunkt. /
Memory funct.
Default Parameter: returns all parameters to the factory settings.
Reset Betriebsdaten: returns all user level parameters to the
factory settings.
Reset Fehler: resets a permanent error.
T-Start
Grid synchronization start timer.
T-Stop
Stop timer for aborting the supply of power and switching off.
Uac-Min
Uac-Max
Lower (Uac-Min) and upper (Uac-Max) limits of the allowable
AC voltage (stand-alone grid recognition), before the grid
monitoring system disconnects the device from the grid.
Name
Explanation
Содержание Windy Boy WB 1100LV
Страница 2: ......
Страница 6: ...Explanation of Symbols Used SMA Technologie AG Page 6 WB1100LV 11 FE2606 User Manual...
Страница 10: ...Safety Instructions SMA Technologie AG Page 10 WB1100LV 11 FE2606 User Manual...
Страница 28: ...Unit Description SMA Technologie AG Page 28 WB1100LV 11 FE2606 User Manual...
Страница 30: ...Setting the Display Language SMA Technologie AG Page 30 WB1100LV 11 FE2606 User Manual...
Страница 40: ...Turbine Operation SMA Technologie AG Page 40 WB1100LV 11 FE2606 User Manual...
Страница 42: ...Maintenance and Care SMA Technologie AG Page 42 WB1100LV 11 FE2606 User Manual...
Страница 50: ...Extensions SMA Technologie AG Page 50 WB1100LV 11 FE2606 User Manual...
Страница 54: ...Technical Data SMA Technologie AG Page 54 WB1100LV 11 FE2606 User Manual...
Страница 72: ...General Information SMA Technologie AG Page 72 WB1100LV 11 FE2606 User Manual...
Страница 74: ...Stand Alone Systems SMA Technologie AG Page 74 WB1100LV 11 FE2606 User Manual...
Страница 77: ......