10.1.2 Windy Boy Operating Parameters
10.1.3 Explanation of the Operating Parameters
U-Konst /
V-Const
Constant voltage operation (the input voltage is predefined; the
Windy Boy operates in neither MPP mode nor Turbine mode). In
some cases, this can be set as the operating mode.
Warten /
waiting
The switch-on conditions are not (yet) satisfied.
Unauthorized changes to the operating parameters may result in:
•
injury or accidents due to changed internal safety routines in the
Windy Boy,
•
voiding the Windy Boy's operating approval certificate,
•
voiding the Windy Boy's warranty.
Never change the parameters of your Windy Boy without explicit
authorization and instructions.
Parameters shown in bold are necessary for the programmable wind curve and
for adjusting a wind turbine system to the Windy Boy (see also section 6 "Turbine
Operation" (Page 31)).
Name
Explanation
ACVtgRPro
Voltage rise protection (only relevant for Germany).
Windy Boys can feed into the public grid in Germany with up to
260 V AC. However, DIN VDE 0126-1-1 stipulates that the
average AC voltage over 10 minutes must not exceed 253 V. If
the average over 10 minutes exceeds the threshold value of
253 V, the inverter disconnects itself from the grid. Once the
average over 10 minutes returns to a value of less than 253 V,
the inverter resumes grid feeding. If surge voltage protection is
not required in the relevant grid area (outside Germany), it can
be deactivated by presetting the LDVtgC parameter. In this
event, only the fast cut-off via the Uac-Max parameter
intervenes.
AntiIsland-Ampl
Amplification of the AntiIsland process (alternative anti-islanding
process, which is deactivated for Germany).
Name
Explanation
Содержание Windy Boy WB 1100LV
Страница 2: ......
Страница 6: ...Explanation of Symbols Used SMA Technologie AG Page 6 WB1100LV 11 FE2606 User Manual...
Страница 10: ...Safety Instructions SMA Technologie AG Page 10 WB1100LV 11 FE2606 User Manual...
Страница 28: ...Unit Description SMA Technologie AG Page 28 WB1100LV 11 FE2606 User Manual...
Страница 30: ...Setting the Display Language SMA Technologie AG Page 30 WB1100LV 11 FE2606 User Manual...
Страница 40: ...Turbine Operation SMA Technologie AG Page 40 WB1100LV 11 FE2606 User Manual...
Страница 42: ...Maintenance and Care SMA Technologie AG Page 42 WB1100LV 11 FE2606 User Manual...
Страница 50: ...Extensions SMA Technologie AG Page 50 WB1100LV 11 FE2606 User Manual...
Страница 54: ...Technical Data SMA Technologie AG Page 54 WB1100LV 11 FE2606 User Manual...
Страница 72: ...General Information SMA Technologie AG Page 72 WB1100LV 11 FE2606 User Manual...
Страница 74: ...Stand Alone Systems SMA Technologie AG Page 74 WB1100LV 11 FE2606 User Manual...
Страница 77: ......