Turbine Operation
SMA
Technologie AG
Page 34
WB1100LV-11:FE2606
User Manual
The characteristic curve ends at the maximum permissible DC input voltage of the
Windy Boy, which must never be exceeded.
Shutdown Procedure
If the wind strength is so low that the DC input voltage falls below <Umin> (an internally
calculated minimum level for operation), then the Windy Boy operates without feeding
power into the grid for the period defined in <T-Stop>.
If the DC input voltage increases once more, the <T-Stop> timer is deactivated, and the
Windy Boy resumes according to the defined curve operation.
If the DC input voltage remains beneath <Umin> for the period defined by <T-Stop>,
the Windy Boy switches itself off.
If the DC input voltage no longer suffices for powering the on-board electronics, the
Windy Boy deactivates immediately.
After the switch-off process, the whole process starts from the beginning.
Only change the operating parameters if you know exactly what you are doing!
Содержание Windy Boy WB 1100LV
Страница 2: ......
Страница 6: ...Explanation of Symbols Used SMA Technologie AG Page 6 WB1100LV 11 FE2606 User Manual...
Страница 10: ...Safety Instructions SMA Technologie AG Page 10 WB1100LV 11 FE2606 User Manual...
Страница 28: ...Unit Description SMA Technologie AG Page 28 WB1100LV 11 FE2606 User Manual...
Страница 30: ...Setting the Display Language SMA Technologie AG Page 30 WB1100LV 11 FE2606 User Manual...
Страница 40: ...Turbine Operation SMA Technologie AG Page 40 WB1100LV 11 FE2606 User Manual...
Страница 42: ...Maintenance and Care SMA Technologie AG Page 42 WB1100LV 11 FE2606 User Manual...
Страница 50: ...Extensions SMA Technologie AG Page 50 WB1100LV 11 FE2606 User Manual...
Страница 54: ...Technical Data SMA Technologie AG Page 54 WB1100LV 11 FE2606 User Manual...
Страница 72: ...General Information SMA Technologie AG Page 72 WB1100LV 11 FE2606 User Manual...
Страница 74: ...Stand Alone Systems SMA Technologie AG Page 74 WB1100LV 11 FE2606 User Manual...
Страница 77: ......