SI4248U Manual
User Manual
81
Settings
Inverter Settings (22)
Battery Settings (23)
Name
Range/
Unit
Default
Description
VacNominal
105 - 130
VAC
120
The VacNominal parameter sets the nominal output
voltage of the inverter.
FacNominal
55 - 65
Hz
60
The FacNominal parameter sets the nominal output
frequency of the inverter.
Name
Range/
Unit
Default
Description
VdcBatNomi-
nal
42 - 48
VDC
48
The VdcBatNominal parameter sets the nominal
operating voltage of the inverter.
BatType
VRLA
FLA
VRLA
The BatType parameter selects the type of battery
used in the system.
VRLA
= Valve Regulated Lead Acid
FLA
= Flooded Lead Acid
Once the system is configured, this parameter can
only be changed via „NewBattery“ (installer pass-
word required).
AmpHoursBat
100 -
6000
Ah
100
The BatCapacity parameter sets the total amp-hour
capacity of the battery bank. This parameter needs
to be set when the inverter is first commissioned.
Once the system is configured, this parameter can
only be changed via „NewBattery“ (installer pass-
word required).
AmpdcBatMax
0 - 100
ADC
10
The AmpdcBatMax parameter sets the DC charge
current limit to the batteries.