![SMA Sunny Island 4248U Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/sma/sunny-island-4248u/sunny-island-4248u_installation-and-operating-instructions-manual_1294205067.webp)
SI4248U Manual
Installation Manual
59
Table 1-13: Error Codes
NoMaster
NA
NA
Splitphase configuration no master
found (on slave device)
NoSlave
NA
NA
Splitphase configuration no slave
found (on master device)
RelayFail
VacInverter
VacGenreator
Automatic
acknowledge.
Restart
Relay Failure
TBatHigh
BatTemp >
TBatMax
BatTemp <
TBatMax-2°C
Battery temperature too high
TR-TempOV
T >=101
°
C
T <= 96
°
C
Transformer over temperature
TwoMaster
Receive hand-
shake from
Master device
Automatic
acknowledge.
Restart
Two master devices in splitphase con-
figuration
TwoSlave
Receive hand-
shake from
slave device
Automatic
acknowledge.
Restart
Two slave devices in splitphase config-
uration
VAC-High
VAC > VAC-
Max
VAC < VAC-
Max
High output voltage
VAC-Low
VAC< VAC-
Min
Automatic
acknowledge.
Restart
Low output voltage
VBatHigh
VBat > VBat-
Max
VBat > VBat-
Max
High battery voltage
VBatLow
VBat < VBat-
Min
(for 30 sec-
onds)
VBat > VBat-
Min
Low battery voltage
Watchdog
Automatic
reset
Watchdog reset
Name
Cause
Release
Description
Содержание Sunny Island 4248U
Страница 2: ...SI4248U Installation Guide ii...
Страница 6: ...SI4248U Installation Guide vi...
Страница 74: ...Battery Management SI4248U Manual 66...
Страница 98: ...Battery Management SI4248U Manual 90...
Страница 99: ......