Installer Level Menu Guide
SI4248U Manual
54
FacGenMax
60 - 66
Hz
65
The FacGenMax parameter selects the maximum
frequency the inverter will accept from the genera-
tor. If the generator frequency is greater than this
limit when running unloaded the Sunny Island
4248U will not connect, or, if the generator fre-
quency goes above this limit while connected the
Sunny Island 4248U will disconnect the generator.
FacGenMin
54 - 60
Hz
55
The FacGenMin parameter selects the minimum fre-
quency the inverter will accept from the generator.
If the generator frequency is lower than this limit
when running unloaded the Sunny Island 4248U
will not connect, or, if the generator frequency goes
below this limit while connected the Sunny Island
4248U will disconnect the generator.
GridConnected
Grid-
None,
Grid-
Charge,
Grid-
FeedPV
Grid-
None
Grid connection mode.
GridNone:
No grid operation - Generator limits;
apply (VacGenMin, VacGenMax, FacGenMin,
FacGenMax, DelayVGenLow, PGenRevers).
GridCharge:
Charge only from grid - UL limits;
apply (voltage range 106 V - 131 V, frequency
range 59.32 Hz - 60.48 Hz), no reverse power
accepted.
GridFeedPV:
Charge from grid and feed grid with
Sunny Boy via Sunny Island; (voltage range 106 V -
131 V, frequency range 59.32 Hz - 60.48 Hz),
reverse power limit is 6.72 kW.
DelayVGenLow
500 -
6000
Ms
3000
The DelayVGenLow parameter selects the amount
of time the Sunny Island 4248U will wait before dis-
connecting when the generator voltage or fre-
quency drops below the VacGenMin or FacGenMin
limits.
Transition
Ramp/
Fast
Fast
The Transition parameter selects the way in which
the Sunny Island 4248U will transition from charge
to invert mode when it detects a grid or generator
fault.
Select
Ramp
when Sunny Boy inverters are con-
nected to the system.
Select
Fast
when no Sunny Boy inverters are con-
nected to the system.
PGenRevers
0 - 1000
W
300
Max. reverse power limitation
Name
Range/
Unit
Default
Description