NOTE: In split-phase mode with two Sunny Island 4248U’s connected together,
the slave unit
must
have the battery temperature sensor connected to set the
inverter to “slave” mode. Once the inverter is set to “slave” mode, it does not
require the battery temperature sensor and can be removed. The slave unit sensor
may be installed temporarily; it does not need to be run through conduit.
Figure 1-16 Auxiliary Wiring Terminals
Shield
C
AN_L
C_GND
C
AN_H
Generator Request
Load Shed
(Dry Contact)
Generator Run
(Optional)
Battery Temp.
Internal Fans
CAN Bus
Inverter to Inverter
Communication
Synchronize
(Optional)
(+15, Transistor)
Communication