6 Connection
SMA Solar Technology AG
Operating manual
EDML-10-BE-en-13
33
• 1 ring terminal lug M4 for grounding cable
Requirements for the power supply unit:
• Short-circuit current: < 8 A
• Nominal output power: 18 W
• DC output voltage: 9 V to 36 V
• Compliance with the requirements on current sources with limited power in accordance with
IEC 60950
Requirements for the connection cable for the connection of the power supply unit to the
product:
• Core cross-section: 0.5 mm² to 1.5 mm² (16 AWG to 20 AWG)
• Number of insulated conductors: 3
• Maximum cable length: 3 m (9.8 ft)
Plug assignment:
Plug
Position
Assignment
V−
V+
1
3
2
1
Input voltage 9 to 36 V DC+
2
Input voltage 9 to 36 V DC-
3
Ground (GND)
Grounding cable requirements:
• Core cross-section: 0.5 mm² to 1.5 mm² (16 AWG to 20 AWG)
• Number of insulated conductors: 1
• Maximum cable length: 3 m (9.8 ft)
Procedure:
1. Mount the power supply unit (see the manufacturer manual).
2. Connect the connection cable to the power supply unit (see the manufacturer manual). Make
a note of the insulated conductor colors and trim the unused insulated conductors back to the
cable sheath.
3. Connect the connection cable to the supplied 3-pole
terminal block. To do this, release the screws of the
required terminal points using a suitable tool, plug
the wires into the terminal points and tighten the
screws of the terminal points hand-tight. Observe the
pin assignment.
1
2
V−
V+
4. Trim unused insulated conductors flush with the cable sheath.