6 Connection
SMA Solar Technology AG
Operating manual
EDML-10-BE-en-13
32
Connect the network communication with external nodes
SMA Solar Technology AG recommends using the network port
LAN2
for the network
communication with external nodes (e.g. SCADA system, Sunny Portal). Network port
LAN2
is
preconfigured with the static IP address 192.168.100.22.
Procedure:
1. Plug the RJ45 plug of the network cable into the
network port
LAN2
until the RJ45 plug snaps into
place.
LAN2
LAN1
2
1
P1 RS-232/422/485
P2 RS-232/422/485
USB2.0
HDMI
3
4
2. Connect the other end of the network cable to the network.
6.6
Connecting the Voltage Supply
WARNING
Danger to life due to electric shock
Under fault conditions, when working on the power supply circuit there may be dangerous
voltages present on the product. This can result in death or serious injury.
• For power supply units with a fixed connection, make sure that a disconnection unit (e.g.
miniature circuit breaker) is present outside the power supply unit.
• For power supply units with a plug connection, make sure that the electrical outlet for the
power supply unit is close to the power supply unit.
• The disconnection unit and the electrical outlet for the power supply unit must be freely
accessible at all times.
NOTICE
Damage to the product due to condensation
If the product is moved from a cold environment to a warm environment, condensation may form
in the product. This can damage the product or impair its functionality.
• When there are large temperature differences, wait until the product has reached room
temperature to connect the voltage supply.
• Make sure the product is dry.
Additionally required material (not included in the scope of delivery):
• 1 power supply unit
• 1 AC connection cable
• 1 connection cable for the connection of the power supply unit to the product
• 1 grounding cable