![SMA AS-Box-S.1 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/sma/as-box-s-1/as-box-s-1_technical-description_1294611027.webp)
SMA Solar Technology AG
Mounting
Technical Description
SBU2200-TEN083320
27
• The mounting location and mounting method must be suitable for the weight (approx. 18 kg)
and dimensions.
• Select a solid surface for mounting the device.
• The mounting location must be accessible at all times (do not mount in inaccessible locations).
• An ambient temperature between –25 °C and +60 °C ensures optimum operation.
• Do not expose the device to direct sunlight. Due to overheating, power reductions may occur.
• In a living area, do not mount the unit on plasterboard
etc. walls as otherwise audible vibrations are likely to
result.
The Sunny Backup 2200 can make noises when in use
which can be seen as a nuisance when installed in a
living area.
5.1.3 Observe Minimum Clearances
Observe the following minimum clearances to walls, other devices or objects, in order to guarantee
sufficient heat dissipation.
All external cables are connected through the
underside of the housing. This requires a minimum
clearance of at least 50 cm.
Direction
Minimum clearance
Sides
10 cm
Top
30 cm
Below
50 cm
Front
5 cm
Sufficient Ventilation
When installing the Sunny Backup 2200 in smaller rooms, make sure that adequate
ventilation is available. The device produces heat when operating that must be removed.