![SMA AS-Box-S.1 Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/sma/as-box-s-1/as-box-s-1_technical-description_1294611134.webp)
Sunny Boy
SMA Solar Technology AG
134
SBU2200-TEN083320
Technical Description
1. Establish a communication connection with the Sunny Boy.
2. Navigate to the parameter settings.
3. Set the "Default" parameter to "Offgrid" (stand-alone grid).
The "OffGrid" parameter setting automatically sets the following Sunny Boy parameters to the values
below:
This completes the stand-alone grid parameter settings for the Sunny Boy.
No:
Parameter
Unit
Displayed value
1
I-NiTest
mA
Off (MSD = 0)
2
Uac-Min
V
180
3
Uac-Max
V
260
4
Fac-delta-
lower range in which the Sunny Boy is active relative to f
0
Hz
–4.5 (starting from the base
frequency f
0
)
5
Fac-max+
upper range in which the Sunny Boy is active relative to f
0
Hz
+1.5 (starting from the base
frequency f
0
)
6
dFac-Max
max. rate of change
Hz/s
4
7
Fac-start delta
frequency increase in relation to f
0
, at which point the power
adjustment via frequency begins
Hz
1 (starting from the base
frequency f
0
)
8
Fac-Limit delta
frequency increase in relation to f
0
, at which point the power
adjustment via frequency ends. The output of the Sunny Boy at
this point is 0 W.
Hz
2 (starting from the base
frequency f
0
)
DANGER!
Risk of lethal electric shock.
Risk of feedback if the public grid is down.
• Never operate the Sunny Boy directly on the grid using these settings.
• Only run the Sunny Boys in the Sunny Backup System S using the Automatic Switch
Box S connections specifically provided for this purpose (see section 8.2.2 „PV
System (X2/PV System)“ (75)).
Using the communication bus
If a Sunny Boy and Sunny Backup 2200 are operated together on a communication bus,
the "270.06 ComBaud" parameter in the Sunny Backup 2200 must be set to "1200"
(default).
The Sunny Backup 2200 only communicates through the SMA-Net protocol; Sunny-Net is
not supported.