Parameter Lists
SMA Solar Technology AG
144
SBU2200-TEN083320
Technical Description
230# Set Backup
222
10
ChrgVtgFlo
V
2.25
cell voltage nominal value for float charge
2.25 = VRLA
2.25 = FLA
1.55 = NiCd
depending on the setting in QCG
222
11
BatTmpCps
mV/degC
4.0
battery temperature compensation
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG
222
12
AutoEquChrgEna
Disable
Enable
Enable
activates automatic equalization charge
223# Bat Protection
223
01
BatPro1TmStr
hhmmss
220000
time for starting battery preservation
mode level 1
223
02
BatPro1TmStp
hhmmss
060000
time for stopping battery preservation
mode level 1
223
03
BatPro2TmStr
hhmmss
170000
time for starting battery preservation
mode level 2
223
04
BatPro2TmStp
hhmmss
090000
time for stopping battery preservation
mode level 2
223
05
BatPro1Soc
%
20
SOC limit for preservation mode level
1
223
06
BatPro2Soc
%
15
SOC limit for preservation mode level
2
223
07
BatPro3Soc
%
10
SOC limit for preservation mode level
3
224# Bat Silentmode
224
01
SilentEna
Disable
Enable
Disable
allows silent mode on the grid
224
02
SilentTmFlo
(Stby)
h
3
max. time for float charge until transfer into
silent
224
03
SilentTmMax
(Stby)
h
12
max. time for silent mode until transfer into
float
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description
231# General
231
01
AcSrcFrqDel
Hz
4,8
frequency increase for disconnecting AC
feed-in generators
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description