PJC421 & PJC422

Control Panel - Menu Navigation

MC_0407

Release command

When the control panel is IN COMMAND, Main Workstations and Remote Workstations can release command to allow for other workstations to take 

command. When command is released, an audible signal will be given to indicate that the state of the control panel has changed from IN COMMAND to 

NOT IN COMMAND. If command is released when thrusters are running, the thrusters will stop. 

If a Remote Workstation request command when another Main or Remote Workstation is in command, a notice is displayed informing that another 

workstation is in command. The notice disappears after 3 seconds, or it can be manually closed. 

 

In such a situation, the other workstation must release the command before the command can be transferred.

Release command.

Closes the notice.

PHC-3 

Fault Codes

MC_0117

Fault Code

Description

Cause

Action

10500.0.10

PHC Oil Level - Level Low

Hydraulic oil level is low

"-Limit use of thruster

-Inspect hydraulic oil level

-Check system for leaks and refi ll hydraulic oil"

10500.0.13

PHC Oil Level - Open Circuit

Analog oil level sensor open circuit

"-Sensor not connected or wire break.

-Verify sensor type in parameter 0201

-Disconnect sensor and measure that sensor resistance value is in 

range 0-180ohm."

10501.0.11

PHC Oil Temp - Level High

Oil temperature higher than 75°C (167°F)

"-Limit use of thruster to prevent temperature to rise.

-Check if cooling pump is running and there is cooling water flow.

-Inspect seawater fi lter

-Verify that cooling pump is enabled in parameter 0301"

10501.0.13

PHC Oil Temp - Open Circuit

Analog oil temp sensor open circuit

"-Sensor not connected or wire break.

- Disconnect sensor and measure that sensor resistance value is in 

range 104ohm-147Kohm

-Wrong sensor is defi ned in parameter 0201"

10501.0.16

PHC Oil Temp - Short Circuit

Analog oil temp input short circuit

"-Input shorted to GND, check wiring/sensor

-Disconnect sensor and measure that sensor resistance value is in 

range 104ohm-147Kohm"

10502.0.13

PHC Stabilizer Pressure - Open Circuit

Stabilizer pressure sensor open circuit

"-Sensor not connected or wire break.

-System incorrectly confi gured with stabilizer, parameter 1001  

-Replace sensor"

10502.0.16

PHC Stabilizer Pressure - Short Circuit

Stabilizer pressure sensor short circuit

"-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor"

10502.0.19

PHC Stablizier Pressure - Under Limit

Stabilizer pressure has dropped below 20bar.

"-Check accumulator charge pressure

-Check PTO pressure (if PTO powered)

-Check system for oil leaks

-Check generator power supply to the VFD (is VFD motor speed 

maximum when pressure alarming low)"

10502.0.20

PHC Stablizier Pressure - Over Limit

"Stabilizer pressure is higher than:

parameter 1013 PTO OVER-PRESSURE FAULT LEVEL running 

from PTO (FW V1.029 an older, set point + 30bar running 

from PTO)

or set point + 15bar running from AC motor"

"-Check Parameter 1013 PTO OVER-PRESSURE FAULT LEVEL

-Check PTO pressure setting

-Check accumulator charge pressure

-Check unload valve operation"

10502.0.26

PHC Stablizier Pressure - VALUE MAX

Stabilizer pressure reached sensor max value.

"-Check that correct sensor is fi tted

-Check that sensor range parameter 1010 match the sensor

-Check PTO pressure setting"

10502.0.200

PHC Stablizier Pressure - Timeout

Stabilizer pressure has not reached 60% of set point parame-

ter 1003 after 30sec.

"-Check pump feed shutoff valve.

-Check PTO pressure (if PTO powered)

-Check system for oil leaks"

10503.0.13

PHC System Pressure - Open Circuit

System pressure sensor open circuit

"-Sensor not connected or wire break.

-Verify system pressure, parameter 0104"

10503.0.16

PHC System Pressure - Short Circuit

System pressure sensor short circuit

"-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor"

10504.0.13

PHC AI 1 - Open Circuit

Analog Input 1 (4-20mA) sensor open circuit

-Sensor not connected or wire break.

10504.0.16

PHC AI 1 - Short Circuit

Analog Input 1 (4-20mA) sensor short circuit

"-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor"

10505.0.13

PHC AI 2 - Open Circuit

Analog Input 2 (4-20mA) sensor open circuit

-Sensor not connected or wire break.

10505.0.16

PHC AI 2 - Short Circuit

Analog Input 2 (4-20mA) sensor short circuit

"-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor"

10508.0.13

PHC DOUT AC PUMP UNLOAD - Open Circuit

AC Pump Unload valve open circuit

"-Check for open circuit, power consumption < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001"

10508.0.51

PHC DOUT AC PUMP UNLOAD - Current High

AC Pump Unload valve current higher than 4.0A

-Check wires and connections for short circuit

10509.0.13

PHC DOUT ACCUMULATOR DUMP - Open 

Circuit

Accumulator Dump valve open circuit

"-Check for open circuit, power < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001"

10509.0.51

PHC DOUT ACCUMULATOR DUMP - Current 

High

Accumulator Dump valve current higher than 4.0A

-Check wires and connections for short circuit

10510.0.13

PHC DOUT STABILIZER - Open Circuit

Stabilizer valve open circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001"

10510.0.51

PHC DOUT STABILIZER - Current High

Stabilizer valve current higher than 4.0A

-Check wires and connections for short circuit

10511.0.13

PHC DOUT COOLING PUMP HYDRAULIC - Open 

Circuit

Hydraulic Cooling Pump valve open circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Wrong cooling pump confi gured, parameter 0301"

10511.0.51

PHC DOUT COOLING PUMP HYDRAULIC - 

Current High

Hydraulic Cooling Pump valve current higher than 4.0A

-Check wires and connections for short circuit

10512.0.13

PHC DOUT LS DUMP - Open Circuit

LS-Dump valve open circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-System wrong confi gured with thrusters, parameter 2001 or 

2101"

10512.0.51

PHC DOUT LS DUMP - Current High

LS-Dump valve current higher than 4.0A

-Check wires and connections for short circuit

10513.0.51

PHC DOUT PUMP #2 - Current High

Pump #2 valve current higher than 4.0A

-Check wires and connections for short circuit

10514.0.13

PHC DOUT 5 - Open Circuit

Digital Output 5 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0505"

10514.0.51

PHC DOUT 5 - Current High

Digital Output 5 current higher than 4.0A

-Check wires and connections for short circuit

10515.0.13

PHC DOUT 6 - Open Circuit

Digital Output 6 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0506"

Содержание PJC421

Страница 1: ...stad Norway www sleipnergroup com DOCUMENT ID REVISION DATE LANGUAGE To download your language go to www sleipnergroup com 6770 2 K e e p t h i s m a n u a l o n b o a r d 2021 EN Including Installati...

Страница 2: ...detent thruster control and S link Color LCD touch screen PJC422 LF90X Dual lever detent thruster control and S link Color LCD touch screen PJC422 LF90X DNV Dual lever detent thruster control and S li...

Страница 3: ...18 Responsibility of the User Operating Thrusters Always turn the control device off when the thruster is not in use or when leaving the boat When leaving the boat always turn off the main power switc...

Страница 4: ...mmediate stop thruster operation Push for 2 seconds to disable the stop function Up and down menu navigation Dedicated functions in dashboard view Press for 2 seconds to turn the panel ON or OFF Adjus...

Страница 5: ...ating temperature 25 C to 70 C IEC 60068 2 1 2007 Cold test IEC 60068 2 2 2007 Dry heat test IP rating IP x7 IEC 60529 EMC tested IEC 60945 2002 IEC 60533 2015 Vibration IEC 60068 2 6 Damp heat IEC 60...

Страница 6: ...only one hydraulic oil temperature symbol for installations where one PHC 3 hydraulic controller is used to control two thrusters The temperature icon has five levels Green signifies normal temperatu...

Страница 7: ...n on how to associate and configure devices see System Devices chapter Configuring more than one associated device to be in the same location will result in a setup conflict Thruster operation is susp...

Страница 8: ...P 35 to mute the audible alarm signals on all Sleipner control panels that are turned on and connected to the S Link bus Unmuted alarms are listed in red and muted alarms are listed in dark blue Activ...

Страница 9: ...e STOP message and then broadcast the STOP Activated message If the STOP Activated message is not received by TP 35 within 1 second after the STOP button is pushed the STOP notice will be closed The S...

Страница 10: ...option De nes functionality of Left Selection button Panel buttons and touch screen functionality can be both used to operate the TP 35 control panel The functionalities of the Selection buttons are...

Страница 11: ...Stern Bow Starboard Stern Starboard Use Bow or Stern in conventional thruster system In a system with two bow or two stern thrusters for example a catamaran Use Bow or Stern for the port thruster For...

Страница 12: ...Direction Stern Thrust Direction PHC 3 Con guration The proportional hydraulic controller PHC 3 has several parameters that can be configured All these parameters are available for configuration on t...

Страница 13: ...90 LF90X Joystick settings The Joystick Setting menu is used to calibrate the joystick None will be displayed if no calibration has been done If a calibration has been done the selected joystick type...

Страница 14: ...stick It is important to keep the joystick in the specified position while pressing Below is an example of the steps for calibrating a dual joystick Control Panel Menu Navigation MC_0407 Abort joystic...

Страница 15: ...isables the Select station functionality Activated Deactivated Defines the type of workstation Main Remote Defines the location of the control panel Only used in systems with Voyage Data Recorder Inte...

Страница 16: ...e thruster dashboard view See the System Devices chapter for more information on configuring the TMU 1 The thruster dashboard view example below shows an installation with four AC thrusters with an RP...

Страница 17: ...ew Operation of joysticks connected to a remote control panel being IN COMMAND will be shown with light blue arrows on the thruster dashboard view The measured RPM of the thruster motor is always disp...

Страница 18: ...of the control panel has changed from IN COMMAND to NOT IN COMMAND If command is released when thrusters are running the thrusters will stop If a Remote Workstation request command when another Main...

Страница 19: ...essure parameter 0104 10503 0 16 PHC System Pressure Short Circuit System pressure sensor short circuit Wires shorted or sensor defective check wiring sensor Replace sensor 10504 0 13 PHC AI 1 Open Ci...

Страница 20: ...A Check all bow and stern PVG signal wires for short circuits 10524 0 51 PHC ECI Cooling Pump Current High ECI cooling pump current higher than 13 0A Check ECI cooling pump cable for damage and short...

Страница 21: ...ult VFD faulted See VFD for more information 36100 1 100 VFD Instance 1 No Communication PDC 301 has no MODBUS communication with VFD Check communication cable with VFD Check if VFD has power 36101 1...

Страница 22: ...ficient troubleshooting if necessary The installer must read this document to ensure necessary familiarity with the product before installation Instructions in this document cannot be guaranteed to co...

Страница 23: ...to the back surface of the dash board to allow for the installation process When deciding your installation preference ensure to 1 Find a suitable location for the control panel where it does not obs...

Страница 24: ...nt Installation TP 35 Top Mount installation 1 Place the supplied cut out template on the desired installation location 2 Cut out the area according to the template 3 Place the gasket to the back face...

Страница 25: ...n the milled area using the template as a guide NB How to secure these studs will depend on the material of the dashboard Insert the control panel in place and fasten with a washer nut NB Fastening bo...

Страница 26: ...ashboard not inc cables 23 5 0 9 c Cable bend radius 35 1 4 TP 35 Top Mount MC_0392 Measurements TP 35 Top Mount MG_0475 H W a b Flush mount c Measurement code Measurement description mm inch H Panel...

Страница 27: ...ied cut out template on the desired installation location 2 Cut out the area according to the template 3 Plug cable into the cable connector at the rear of the TP 35 control panel NB During the TP 35...

Страница 28: ...nt code Measurement description mm inch H Panel Height 123 4 4 9 W Panel width 105 5 4 1 a Raised height above the dashboard 111 3 4 4 b Depth behind the dashboard not inc cables 94 7 3 7 c Cable bend...

Страница 29: ...anel Installation 1 Place the supplied cut out template on the desired installation location 2 Cut out the area according to the template 3 Plug both cables from the control panel into a S Link T conn...

Страница 30: ...ment code Measurement description mm inch H Panel Height 206 8 1 W Panel width 106 4 2 a Raised height above the dashboard 111 3 4 4 b Depth behind the dashboard not inc cables 94 7 3 7 c Cable bend r...

Страница 31: ...the gasket to the back face of the panel If the front surface around your cut out is jagged or chipped use a sealant to assist the gasket 4 Plug cables into the connectors at the rear of the control...

Страница 32: ...ent description mm inch mm inch H Panel Height 96 3 8 96 3 8 W Panel width 96 3 8 96 3 8 a Raised height above the dashboard 98 8 3 9 98 8 3 9 b Depth behind the dashboard not inc cables 94 3 7 94 3 7...

Страница 33: ...detent point 10 use 3mm Hex Key Use DIP switch to set back light color of LE90 Turning ON all three colors enables white light Use switch to con gure power source for LE90 backlight Choose Panel to p...

Страница 34: ...description mm inch mm inch H Panel Height 96 3 8 96 3 8 W Panel width 96 3 8 96 3 8 a Raised height above the dashboard 104 7 4 1 104 7 4 1 b Depth behind the dashboard not inc cables 17 2 0 7 17 2...

Страница 35: ...the template 3 Plug cable into the cable connector at the rear of the TP 35 control panel NB During the TP 35 panel installation this cable may already be attached if access to the back side of the c...

Страница 36: ...t description mm inch mm inch H Panel Height 96 3 8 96 3 8 W Panel width 96 3 8 96 3 8 a Raised height above the dashboard 112 5 4 4 112 5 4 4 b Depth behind the dashboard not inc cables 85 3 3 85 3 3...

Страница 37: ...Max current on 5V to joystick 40mA Intended for joystick potentiometers Max current on 5V to joystick LED 80mA Intended for joystick backlight IO protection 31VDC and 0VDC All accessible IOs tolerate...

Страница 38: ...shall be connected to GND and the red wire connected to 12VDC or 24VDC To reduce the risk of interference avoid routing the S Link cables close to equipment such as radio transmitters antennas or hig...

Страница 39: ...n Serial number ie Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedu...

Страница 40: ...ned to the Purchaser at the Warrantor s expense If on the other hand the claim is determined to result from circumstances such as described in section 4 above or a result of wear and tear exceeding th...

Страница 41: ...41 6770 2 2021 PJC421 PJC422 13 1 13 1 4 0 4x 127 6 96 1 83 0 78 9 110 4 114 5 95 5 127 7 TP 35 Top Mount...

Страница 42: ...42 6770 2 2021 PJC421 PJC422 7 0 4x 89 1 120 6 9 9 9 9 82 1 113 6 3 5 3 5 Milling depth 3 5mm 95 5 127 0 10 0 4xStud positions TP 35 Flush Mount...

Страница 43: ...43 6770 2 2021 PJC421 PJC422 6 5 94 5 112 4 74 0 74 0 10 4x 4x 3 PJC421 PVREL...

Страница 44: ...44 6770 2 2021 PJC421 PJC422 84 0 166 0 74 0 156 0 98 0 6 5 95 0 195 0 10 4x 6x 3 PJC422 PVREL...

Страница 45: ...45 6770 2 2021 PJC421 PJC422 4 x 5 5mm 17 25 79 0 78 5 44 0 74 0 PJC421 LF90 PJC422 LF90...

Страница 46: ...46 6770 2 2021 PJC421 PJC422 4x 5 5mm 70 0 79 2 79 2 39 6 39 6 PJC421 LE90 PJC422 LE90...

Страница 47: ...47 6770 2 2021 PJC421 PJC422 74 0 47 0 79 2 79 2 2 6 16 1 PJC421 LF90X PJC422 LF90X...

Страница 48: ...422 LE90 PJC422 LE90 DNV PJC421 LF90X PJC421 LF90X DNV PJC422 LF90X PJC422 LF90X DNV PJC421 LF90 PJC421 LF90 DNV PJC422 LF90 PJC422 LF90 DNV Subject to installation maintenance and use conforming to t...

Страница 49: ...PJC422 LE90 PJC422 LE90 DNV PJC421 LF90X PJC421 LF90X DNV PJC422 LF90X PJC422 LF90X DNV PJC421 LF90 PJC421 LF90 DNV PJC422 LF90 PJC422 LF90 DNV Subject to installation maintenance and use conforming...

Страница 50: ...50 6770 2 2021 PJC421 PJC422 MC_0037 Notes...

Страница 51: ...51 6770 2 2021 PJC421 PJC422 MC_0037 Notes...

Страница 52: ...ccuracies or omissions it may contain Continuous product improvement may change the product specifications without notice Therefore Sleipner Motor AS can not accept liability for any possible differen...

Отзывы: