INSTALLATION AND OPERATING INSTRUCTIONS
SKF Multilog On-line System IMx-16Plus
32 (66)
SKF Multilog On-line System IMx-16Plus
User Manual
Revision Letter A
Figure 17
Example of registration process on first use of the app.
2.5.14 IMx-16Plus Stand-alone mode
The IMx-16Plus can be configured to be used in stand-alone mode. In this scenario,
a connection to the @ptitude Observer Monitor Service is not required as data is not
transferred for trending and analysis by the @ptitude Observer Client. Instead,
measurement data and alarms are displayed in the SKF Multilog IMx Manager app.
Help on using the various functionality of the SKF Multilog IMx Manager app. Is
available in-app.
2.5.15 Time synchronisation
Each IMx-16Plus device has a backup power capacitor which will maintain the time
setting for approximately one week if the device is disconnected from power.
To correct or set/reset the time, use one of the following methods:
•
Automatic time synchronisation
This method is preferable since the IMx will continuously synchronise the
time with the computer that has @ptitude Observer Monitor Service running.
IMx devices use a standard (S)NTP time synchronisation protocol supported
by the Windows Time service.
To activate time synchronisation, refer to the Time Synchronisation chapter in
the "@ptitude Observer Installation Manual".