INSTALLATION AND OPERATING INSTRUCTIONS
Power requirements
SKF Multilog On-line System IMx-16Plus
User Manual
Revision Letter A
19 (66)
Important safety warnings:
The system power supply must be provided with an appropriately
positioned, clearly labelled full pole isolator or switch that can be used to isolate
and lock-out power from the IMx-16Plus unit during installation, maintenance or
modification work. The switch must be labelled "IMx-16Plus
” or similar
, with clear
identification of which IMx, if multiple units are deployed. The On/Off position
must be clearly marked.
The supply scheme should also incorporate suitable fusing or circuit breakers.
To prevent a hazardous event, power cable return and positive wires must
be secured together with a cable tie (for example, a nylon cable tie CV-100K)
close to the power connections, at the IMx-16Plus unit.
Figure 5
Example of securing positive and return wires with a cable tie
To connect the IMx-16Plus to the DC power supply, use cable of the
following standard or better:
FKLK 3 x 1,5 mm
2
(16 AWG) or EKLK 3 x 1,5 mm
2
(16 AWG) or corresponding,
with minimum voltage requirement 300 V and temperature
range of −40 to
+70 ºC (−40 to +158 °F).
The power supply cable must be properly fixed to prevent strain, twist or
movement. Always use an appropriate cable gland at entry to any outer
enclosure and cable trunking or similar within it.