Document NO.: RD-690-39-001 Version: A Date
:
2017.12.30
7.2 Service Functions
The following Menu Items will assist in ensuring the fire detection and alarm system operates at optimal performance.
Menu
Item
Preference
Title
Description
1-1
Display historic log
A rolling list of 4000 events are stored. The log assist in
forensic analysis of past events and can be used to
determine the timing and any relationship between
events.
1-2
Read/clear auto start count
Each time power is applied to the equipment, the count
increments. The count can assist in determining if
power if interrupted in an uncontrolled or intermittent
manner.
A system reset does not increment the count.
6-1
Device count, Type & value
The status of devices connected to the analogue loop,
including device type, value and dynamic analogue
sensing value, can be reviewed.
The function can be used to check that all loop devices
are present and to confirm the device address.
In installation Mode, the device count will change as the
control and indicating equipment detects additions or
removal of devices.
In Active Mode, the device value is dynamic.
Service intervals may be set by local regulations.
7.3 Inspections
Conduct the following inspections every 6 months.
1)
Inspect detectors for any condition that is likely to adversely affect their operation, such as excessive deposition of
dust or coating of paint.
2)
Inspect battery condition for signs of corrosion.
3)
Inspect manual call points for clearance and ease of access.
4)
Inspect alarm devices for clearance, visibility, and marking
5)
Inspect the documentation to ensure it is available and complete.
7.4 Tests
7.4.1 6 Monthly Tests
Conduct the following tests every 6 months.
1)
Test that an alarm simulated from a detection zone causes the Alarm Condition and all required outputs (e.g. alarm
devices, output relays) activate, including any delayed outputs. Confirm that all required visual and audible
indications and outputs activate at the control panel.
2)
Test that a Fault Condition occurs for the following events:
Содержание GS690
Страница 18: ...18 Document NO RD 690 39 001 Version A Date 2017 12 30 Figure 11 Figure 12 ...
Страница 27: ...27 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 29: ...29 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 30: ...30 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 31: ...31 Document NO RD 690 39 001 Version A Date 2017 12 30 ...