Document NO.: RD-690-39-001 Version: A Date
:
2017.12.30
The delay time of evacuation can be configured. When a fire signal is received, the timer commences a countdown.
Upon expiry of the pre-set time, the audio/visual alarm will be activated. The maximum delay time is 10 min.
Three optional settings may be selected:
DISABLED, where the timer is inactive, and audio/visual alarm devices do not operate upon the receipt of a fire
signal.
DEVICE MODE, where the timer is initiated upon the receipt of a fire signal from a specific device.
GLOBAL MODE, where the timer is initiated upon the receipt of any fire signal.
Where DEVICE MODE is selected, at least one device must be configured to start the timer (see Menu Item 7-1-5).
When the alarm timer is initiated, the SILENCE/ALARM key will not cancel the timer, although it will
SILENCE/ALARM devices that are not subject to the time delay.
4.3.8.4.2
Operation
1)
By pressing the
【
4
】
key from the General screen enters into the Config Eva-Timer mode
2)
Press direction keys to select Mins, Secs and status.
3)
Press
【
ENTER
】
key to confirm the selection and it will automatically return to previous menu.
4.3.8.5 Dev Eva-Timer (Menu Item 7-1-5)
4.3.8.5.1
Description
Specific devices that initiate the evacuation delay timer (see Menu Item 7-1-4) can be configured.
This function is only operational when the alarm delay timer mode is set to DEVICE MODE.
4.3.8.5.2
Operation
1)
By pressing the
【
5
】
key from the General screen enters into the Dev Eva-Timer mode.
2)
Press direction keys to select loop number, devices number and the status of timer.
3)
Select the status of timer UNAFFECTED or STARTED.
4)
Press
【
ENTER
】
key to confirm the selection and it will change to the next device.
5)
Press
【
MENU
】
key to return to previous menu.
4.3.9
Special Features
4.3.9.1 Pre-alarm
Control panel setup in pre-alarm status, the pre-alarm indicator would flash when a device caused an
alarm.
4.3.9.1.1
Description
Any two devices can be configured to activate evacuation. it means when both of devices at same time detect the fire
DD/MM/YY <Panel Status> HH:MM:SS
1. Two Dev-Evacuate 4.Main Panel ID
2. Call Point Evacuate
3. NAC Status [General]
Содержание GS690
Страница 18: ...18 Document NO RD 690 39 001 Version A Date 2017 12 30 Figure 11 Figure 12 ...
Страница 27: ...27 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 29: ...29 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 30: ...30 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 31: ...31 Document NO RD 690 39 001 Version A Date 2017 12 30 ...