86
mode; The set point should be the smaller one between “
T-Water tank
” +5°C and 60°C in “
Hot water
” mode.
2.The water pump for other thermal must be always active under the “Heat” mode.
3.Under the “
Heat
” mode, the 2-way valve will be controlled based on the setting of the control panel. During
heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water
pump will start but the other thermal will stop.
Under the “
Hot water
” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will
always stop but the other thermal will start.
Under the “
Heat + Hot water
” mode, the other thermal only works for space heating, and the electric heater
of the water tank works for water heating. In this case, the 2-way valve is controlled base d on the setting of the
control panel, and the 3-way valve will always stop. During heating operation, the water pump of the heat pump
unit will be stopped; however, during standby status, the water pump will start.
Logic 2
1.The set point of other thermal should be equal to that of “
WOT-Heat”
and both are or lower than 60
℃
in “
Heat
”
mode and “
Heat + hot water
”mode; The set point should be the smaller one between “
T-Water tank
” +5°C and
60°C in “
Hot water
” mode.
2.The water pump for other thermal must be always active under the “
Heat
” mode.
3.Under the “
Heat
” mode, the 2-way valve will be controlled based on the setting of the control panel. During
heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water
pump will start but the other thermal will stop.
Under the “
Hot water
” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will
always stop but the other thermal will start.
Under the “
Heat + Hot water
” mode (“
Heat
” takes the priority), the other thermal only works for space heating,
and the electric heater of the water tank works for water heating. In this case, the 2-way valve is controlled base d
on the setting of the control panel, and the 3-way valve will always stop. During heating operation, the water pump
of the heat pump unit will be stopped; however, during standby status, the water pump will start.
Under the “
Heat + Hot water
” mode (“
Hot water
” takes the priority), the other thermal works for space heating
and water heating. The other thermal will work for water heating firstly, after reached “
T-water tank
”, it will trun to
space heating mode.
Logic 3
The heat pump will only send a signal to other thermal, but all the logic of control must be “
stand alone
”.
Other Thermal Control
No.
Product
Mode
Remark
Required accessories
Logic 1
Monobloc
Heat
/
Available
RT5 temperature sensor
Hot water
/
Available
Extra 3-way valve, water tank sensor
Heat+Hot
water
/
Available
RT5 temperature sensor, water tank sensor
Split
Heat
/
Available
RT5 temperature sensor
Hot water
/
Available
Extra 3-way valve, water tank sensor
Heat+Hot
water
/
Available
RT5 temperature sensor, water tank sensor
All in One
Heat
/
Available
RT5 temperature sensor
Hot water
/
Not available
/
Heat+Hot
water
/
Available
RT5 temperature sensor, water tank sensor
Содержание GSH ERB-3 Series
Страница 1: ...GSH XXXTRB2 GSH XXXERB2 GSH XXXTRB2 3 GSH XXXERB 3 SPLIT HEAT PUMPS SERVICE MANUAL H E A T P U M P S...
Страница 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Страница 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Страница 55: ...51 13 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 Parts List of GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3...
Страница 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Страница 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Страница 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Страница 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...