144
3.4 Overload Protection of Compressor or Driver Error
Comp Overload Protection
Check if the AC
contactor is damaged
Replace the AC contactor
Check if the compressor
wiring is correct
Adjust the
compressor wiring
Check if the voltage is normal
Check if the refrigerant of
the system is excessive
Contact the power
supply company
Recharge suitable
amount of the refrigerant
yes
no
no
yes
no
yes
yes
3.5 DC Fan Error EF
EF is displayed on
the wired controller
Is the motor wire
phase sequence right
?
Adjust the motor wire
Is the Fan wire
terminal loose
?
Replace the mainboard AP2.
Does it work normally?
Work Normally
yes
no
yes
no
no
Tighten the fan
wiring terminal
Replace the outdoor fan
yes
Содержание GSH ERB-3 Series
Страница 1: ...GSH XXXTRB2 GSH XXXERB2 GSH XXXTRB2 3 GSH XXXERB 3 SPLIT HEAT PUMPS SERVICE MANUAL H E A T P U M P S...
Страница 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Страница 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Страница 55: ...51 13 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 Parts List of GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3...
Страница 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Страница 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Страница 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Страница 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...