82
3.2.4 Commissioning Parameter Setting
[Operation Instructions]
1.At the menu page, by touching “
Commission
”, it will access to the commissioning parameter page, where the
left side is for the function setting and the right side is for the parameter setting, as shown in the figure below.
[Notes]
●At the commissioning parameter setting page, when the state of any function changes, the system will
automatically save this change and this change will remain upon power failure.
●Do not modify any commissioning parameter except the approved qualified servicemen, as it would cause
adverse effects to the unit.
Commissioning Function Setting
No.
Item
Range
Default
Description
1
Ctrl. state
T-water out/T-room
T-water out
When “
Remote sensor
” is set to “
With
”, it can
be set to “
T-room
”.
2
2-Way
valve
Cool 2-Way valve, On/Off
Off
It will decide the status of the 2-way valve under
the “
Cool
” and “
Cool + Hot water
” modes.
Under “Cool” or “Cool + Hot water” mode,
the status of the 2-way valve depends on this
setting. This setting is unavailable to heating
only units.
Heat 2-Way valve, On/Off
On
It will decide the status of the 2-way valve under
the “
Heat
” and “
Heat + Hot water
” modes
5
Solar
setting
With/Without
Without
When the water tank is unavailable, this setting
will be reserved.
When it is set to “
With
”, the solar kitting will work
on its own.
When it is set to “
Without
”, hot water by the
solar kitting is unavailable.
6
Water tank
With/Without
Without
Unavailable to mini chillers.
7
Thermostat
Without/Air/Air+ hot water
Without
This setting cannot be interchanged between
“
Air
” and “
Air+ hot water
” directly but via
“Without” this option
On/Off
Off
This setting is available to mini chillers.
8
Other
thermal
With/Without
Without
/
9
Optional
E-Heater
Off/1/2
Off
/
10
Remote
sensor
With/Without
Without
When it set to “Without”, and the “Ctrl. state” will
be defaulted to be “T-water out”.
11
Air removal
On/Off
Off
/
12
Floor debug
On/Off
Off
/
Содержание GSH ERB-3 Series
Страница 1: ...GSH XXXTRB2 GSH XXXERB2 GSH XXXTRB2 3 GSH XXXERB 3 SPLIT HEAT PUMPS SERVICE MANUAL H E A T P U M P S...
Страница 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Страница 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Страница 55: ...51 13 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 Parts List of GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3...
Страница 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Страница 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Страница 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Страница 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...