11
Model
Power Supply
Leakage
Leakage
Switch
Minimum
Sectional
Area of Earth Wire
Minimum
Sectional
Area of Power
Supply Wire
V,Ph,Hz
(A)
(mm
2
)
(mm
2
)
GSH-80ERB
230VAC,1Ph,50Hz
25
4.0
4.0
GSH-100ERB
25
4.0
4.0
GSH-80TRB
40
6.0
6.0
GSH-100TRB
40
6.0
6.0
GSH-80ERB2
25
4.0
4.0
GSH-100ERB2
25
4.0
4.0
GSH-80TRB2
40
6.0
6.0
GSH-100TRB2
40
6.0
6.0
GSH-80ERB-3
400V,3N~,50Hz
16
2.5
2.5
GSH-100ERB-3
16
2.5
2.5
GSH-80TRB2-3
20
4.0
4.0
GSH-100TRB2-3
20
4.0
4.0
GSH-120ERB-3
16
2.5
2.5
GSH-140ERB-3
16
2.5
2.5
GSH-160ERB-3
16
2.5
2.5
GSH-120TRB2-3
20
4.0
4.0
GSH-140TRB2-3
20
4.0
4.0
GSH-160TRB2-3
20
4.0
4.0
GSH-120ERB
230VAC,1Ph,50Hz
32
6.0
6.0
GSH-140ERB
40
6.0
6.0
GSH-160ERB
40
6.0
6.0
GSH-120TRB2
40
6.0
6.0
GSH-140TRB2
40
6.0
6.0
GSH-160TRB2
40
6.0
6.0
Notes
(a)
Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in use,
action response time must be less than 0.1 second, leakage circuit must be 30mA.
(b) The above selected power cable diameters are determined based on assumption of distance from the
distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of
power cable must be increased to a further grade.
(c) The power supply must be of rated voltage of the unit and special electrical line for air-conditioning.
(d) All electrical installation shall be carried out by professional technicians in accordance with the local laws
and regulations.
(e) Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment of
the building and must be installed by professional technicians.
(f)
The specifications of the breaker and power cable listed in the table above are determined based on the
maximum power (maximum amps) of the unit.
(g)
The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire
copper cable (like, YJV XLPE insulated power cable) used at 40°C and resistible to 90°C (see IEC 60364-5-
52). If the working condition changes, they should be modified according to the related national standard.
(h)
The specifications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40°C. If the working condition changes, they should be modified according to the related
national standard.
(i)
A circuit breaker must be added to the fixed line. The circuit breaker is all-pole disconnected and the
breaking distance of the contact is at least 3mm.
Содержание GSH ERB-3 Series
Страница 1: ...GSH XXXTRB2 GSH XXXERB2 GSH XXXTRB2 3 GSH XXXERB 3 SPLIT HEAT PUMPS SERVICE MANUAL H E A T P U M P S...
Страница 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Страница 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Страница 55: ...51 13 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 Parts List of GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3...
Страница 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Страница 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Страница 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Страница 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...