1.4 Design Principle
(1) Cooling: capacity of the unit ≥ cooling load of the air conditioning
(2) Heating: capacity of the unit ≥ max{ heating load, floor heating load, water heating load}
(3) Water Tank: it should be selected based on the sanitary outfit or quantity of users. Each unit can
accommodate only one water tank.
2 Selection of the Underfloor Coils
2.1 Calculation of Unit Load for Floor Heating
Empirical Values of Floor Heating Load Per Square Meter
House W/m
2
Dining Room
100~120
Master Room
100~110
Guest Room
110~130
Study Room
90~110
Villa W/m
2
Dining Room
110~140
Master Room
100~120
Guest Room
100~130
Study Room
100~120
Notes:
(1) Villas whose load is generally larger than the houses should take the value between the middle and the
maximum empirical values listed above.
(2) The top layer whose load is generally larger than the middle or bottom layer should take the maximum
empirical value.
(3) The guest room whose load is generally much large should take the value between the intermediate and
the maximum empirical values listed above.
(4) For those whose external walls or glass areas are large, it is recommended to take the load calculation.
(5) The heating load for the bathroom is generally 500W/room.
2.2 Selection of Tube Spacing of the Underfloor Coils
Tube spacing of the underfloor coils which will directly affect heat dissipation of the floor depends on the tube
material, indoor design temperature, supply water temperature and floor material.
Heat Dissipation of Commonly Used Coils
(Tube material: PE-X, Indoor temperature:18°C, Average water temperature:45°C)
Floor
Material
Thermal Resistance
m
2
·K/W
Tube Spacing
mm
Heat Dissipation
W/m
2
Tube Spacing
mm
Heat
Dissipation
W/m
2
Stone
0.02
200
147.0
150
159.8
Wood
0.075
200
111.2
150
117.8
The dissipated heat of the floor coil is larger than the load for the floor heating system; however the deviation
cannot be larger than 10%.
2.3 Selection of Loop Quantity of Coils for Each Room
2.3.1 Type of Underfloor Coils
When selecting underfloor coils, we should consider both their comfortability and heating capacity. The most
commonly used coils are as shown below.
Содержание GSH ERB-3 Series
Страница 1: ...GSH XXXTRB2 GSH XXXERB2 GSH XXXTRB2 3 GSH XXXERB 3 SPLIT HEAT PUMPS SERVICE MANUAL H E A T P U M P S...
Страница 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Страница 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Страница 55: ...51 13 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 Parts List of GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3...
Страница 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Страница 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Страница 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Страница 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Страница 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...