be read correctly at startup. Try isolating and de-isolating something (e.g. bells) to get the controller to
retry writing/reading this RAM.
13.
EEPROM write fail
This fault will occur if a failure occurs when writing to EEPROM database memory during program
mode.
14.
All MAF zones isolated
This fault will occur if all zones (mapped to MAF) are isolated. This can be inhibited with an option in
programming, but doing so contravenes AS1603.4.
15.
Supply failed
This fault means that both mains have failed and the battery voltage has fallen to 21 volts or below.
The standby relay is de-energised and all processing of circuit inputs stops.
16.
Output logic exec error nn
An error has occurred with output logic execution. The error number nn has the following meaning:
NOTE:
The software produces the following error messages from a series of built-in checks which are
performed during the operating of the FIP outputs. It is highly unlikely that such errors will occur. If
one does, the operator should inform the service company and have them check it.
“No equations have been found but some were expected”. This indicates a
conflict in the information stored in the EEPROM database.
Invalid Opcode - An invalid token has been encountered in an equation.
Range error - This occurs when an out of range value is found such as a
timer number greater than 64 or an ancillary relay number greater than 3.
Stack error - The execution stack in the RAM has overflowed or under-
flowed.
Link error - An invalid value has been found in a link field in an equation.
Invalid MAF output - This indicates a conflict in information stored in the
EEPROM database. An equation has been found to control an ancillary or
MAF relay but was not expected.
NA (New Alarm) function RAM limit exceeded - This indicates too many NA
functions have been used in the programming of Output Logic functions.
Netvar SID not present - This error occurs if a network variable in the output
logic specifies a SID which is not present in the SID list of this panel. Every
SID for which Netvars are to be accessed must be entered into the SID list
of this panel.
Zone command range error - An equation to isolate/de-isolate or reset a
zone or range of zones had an invalid zone number.
17.
System/Auto Test circuit test fail
A circuit test failed during system or Auto Test or an unexpected fault or alarm occurred during the
test. The Brigade fault relay is turned on when this fault is present. The fault will be cleared by a
successful system or Auto Test. Isolating the faulty circuit & performing a system test should allow the
test to pass & clear the fault.
18.
Shift register bus fault
This error indicates a fault with the bus connecting the Controller with the MAF/PSU, zone modules
and relay modules. It may be caused by a break or short in the flat ribbon cable (e.g. bd unplugged),
by temporary noise, or by a circuit board fault.
NOTE
:
When this fault occurs all processing of inputs stops until the fault clears. If the fault does
clear, processing of inputs resumes automatically.
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...