Page 9 of 60
1.1.2 Loop Card Faults
Description:
If the Loop card (MAPNET or IDNET) is in an ABNORMAL (FAULT) state, all devices on that loop will be
displayed as NORMAL.
This NORMAL indication is used to reduce the number of faults when a Loop is not working as all devices
would be displayed as NO ANSWER.
To confirm a Loop card is in NORMAL status:
Press the MENU button.
Scroll through the options until CARD STATUS is reached.
Press the ENTER button
Scroll through the cards in the panel. Confirm that each loop card is NORMAL.
If
CARD MISSING FAILED ABNORMAL
then press ENTER and Scroll through card faults.
Refer to the relevant section for fault descriptions.
IDNet Loop Voltage = approx24vDC normally & 30vDC when the panel is in alarm
MAPNet Loop Voltage = approx 36vDC at all times.
Note: IDNet & MAPNet Loop Voltages are fluctuating DC because the Loop Voltage is modulated
to transmit the data.
NOTE
-
It is vital that the Loop card is in
NORMAL status before addressable
device fault finding is started.
!
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...