1.1.2.3.4 Extra Device
Description:
A device is located on the addressable loop that is addressed at a location that is not programmed.
Possible causes:
The panel has identified a device/card at an address that is not in the panel programming. Refer to the Extra
Device section of Device Faults (Page 20).
A card/device may be incorrectly addressed bringing up an Extra Device fault and the programmed device‟s
address will display “Points defined but not inserted.”
1.1.2.3.5 IDNet Dipswitch Settings
1. Devices are supplied with DIPSWITCH switch ALL ON (set to 0)
2. DIPSWITCHES are labeled 1 to 8
Switch 1 = MUST BE ON (OFF disables card communications)
Switch 2 = 64
Switch 3 = 32
Switch 4 = 16
Switch 5 = 8
Switch 6 = 4
Switch 7 = 2
Switch 8 = 1
3. Turn Switch
OFF
to add the above number to the address.
Examples:
Address 5 = Switch 6 & 8 OFF all others ON.
Address 23 = Switch 4, 6, 7 & 8 OFF others ON.
NOTE -
This is reverse of how the addressable devices addresses
’ are set.
[Refer to section 1.1.3.9
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...