Page 14 of 60 

 
 

1.1.3.1.2  Head Missing 

 

Description: 

 
The panel is seeing the base at the displayed address but is not seeing the head (Sensor). 
 

Possible causes: 

 

  Head is not installed. 

  Head is not fully twisted onto the base 

  Detector terminals on the base are loose  

  Faulty Head 

  Faulty Base 

 
 

Suggested solutions: 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

NO 

NO 

YES 

Replace Head 

Adjust terminals to 

make better contact 

with head 

Is base LED 

flashing? 

Replace Base 

 

Содержание 4100 Classic

Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...

Страница 2: ...8 Detector LED Operation 18 1 1 3 1 9 Device DIP Switch Settings 18 1 1 3 1 10 End of Line Resistors 19 1 1 5 4100 0157A Battery Charger Faults 21 1 1 6 Positive Negative Earth Ground Faults 23 1 1 6...

Страница 3: ...VER MODULE AND STROBE LIGHT CONNECTION 48 5 4 2 Cable Sizing 48 TABLE 1 CABLE GAUGES 48 5 4 3 Links and DIP Switches 49 TABLE 2 LINK SETTINGS AND THEIR CORRESPONDING OUTPUTS 49 TABLE 3 DIP SWITCHES 1...

Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...

Страница 5: ...up to 4 RUI loops per CPU For larger or multi building sites multiple 4100 series panels can be networked together up to 99 panels or PC based graphic stations each panel or station is called a Node...

Страница 6: ...e Warning or Evacuation System along with any other programmed functions site specific The Operator Interface indicates common Alarm Fault Isolation Status on LEDs and point detector status on the LCD...

Страница 7: ...Number Enter Enter the number of an auxiliary relay point FB Number Enter Enter the number of a feedback point IO Number Enter Enter the number of a 24 Point I O point IDNet 4100U Mapnet earlier 4100...

Страница 8: ...he CPU card is generally the only legacy card vertically mounted with its components side facing in a different direction relative to other cards mounted in a similar fashion otherwise it will be the...

Страница 9: ...ialization Extra Device Card DIP Switch Addressable Device Faults No Answer Head Missing Wrong Device Bad Answer Extra Device Output Abnormal Detector LED Operation Device LED Operation DIP Switch Tab...

Страница 10: ...til CARD STATUS is reached Press the ENTER button Scroll through the cards in the panel Confirm that each loop card is NORMAL If CARD MISSING FAILED ABNORMAL then press ENTER and Scroll through card f...

Страница 11: ...same address 1 1 2 3 Short Circuit Abnormal Description The addressable loop has a short circuit or the and wires are crossed over Possible causes If there are no isolators fitted or the short is betw...

Страница 12: ...nicate with any device on the loop Be aware all devices associated with this loop will indicate a Normal state to prevent multiple faults per display Possible causes The Loop has a Short circuit The L...

Страница 13: ...and the programmed device s address will display Points defined but not inserted 1 1 2 3 5 IDNet Dipswitch Settings 1 Devices are supplied with DIPSWITCH switch ALL ON set to 0 2 DIPSWITCHES are label...

Страница 14: ...lts Refer to the relevant section for fault descriptions 1 1 3 1 1 No Answer Description The panel has a device programmed at the address displayed that is not responding Possible causes 1 Device is n...

Страница 15: ...but is not seeing the head Sensor Possible causes Head is not installed Head is not fully twisted onto the base Detector terminals on the base are loose Faulty Head Faulty Base Suggested solutions NO...

Страница 16: ...correct device installed Relay with T Sense fitted instead of standard Relay Incorrect head installed Photo instead of Heat Detector head not making good contact with base Suggested solutions NO YES R...

Страница 17: ...ill most likely be two different device types Water damaged device or wiring Electrical Interference Suggested solutions No Yes Yes No Find other device on Loop with same address Fault changed to WRON...

Страница 18: ...clear than other faults Possible causes Device not added to the program Device addressed incorrectly Device not programmed at all IDNet address 255 MAPNet address 0 Suggested solutions 1 Device 255 D...

Страница 19: ...field or conventional zone circuit that is programmed for Alarm Verification Check for previous faults and note in the Log book the time and date this fault occurred 1 Log in at Level 4 2 Select P214...

Страница 20: ...MAPNet device address is 127 1 1 3 1 10 End of Line Resistors For a comprehensive pocket reference guide contact your local Simplex branch 4090 9001 Supervised IAM Current Limited 6 8k 4 7k 1 8k 4090...

Страница 21: ...1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 1110 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 0001 8 24 40 5...

Страница 22: ...her To correctly measure the output voltage you will need to follow the steps below 1 To prevent damage to the system disconnect the batteries power down the system disconnect the power comms harnesse...

Страница 23: ...rim pot You may be able to work on it in situ by using a small inspection mirror If not it is recommended that the panel be powered down and the power supply dismounted from the panel and reconnected...

Страница 24: ...s shown below Access Level 3 Passcode 333 Or contact your local Simplex Branch This will then enable the Diagnostics menu option available for selection Choose a Location Search or an IDNet channel Se...

Страница 25: ...il after repeated discharges through them When the earth fault is located on a Mapnet or IDNet loop disconnect one end of the loop from the Loop card both and terminals and break the loop in different...

Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...

Страница 27: ...incompatible firmware revisions CLASS S Crash Indicates a possible error bug in executive software Check the system revision via MENU Software Revision Level and contact your local Simplex branch CLA...

Страница 28: ...E then Rev 4 03 or higher system executive is required Also see FSB 386R The CFIG format Panel Programmer used is incompatible with the panel EXEC installed 32 CRASH_BAD_CONST K_SEG checksum error CLA...

Страница 29: ...H MSGLIB Format error Message library format number is incorrect for system software revision Wrong MSGLIB on programmer disk Use same programmer version to burn upper and lower EXEC chips 67 CRASH_SM...

Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...

Страница 31: ...the Graphical Control Centre setup is site specific It is possible to access a panel directly from the Graphical Control Centre using the Set Host function on a GCC or IMS System or by opening a sess...

Страница 32: ...n be viewed in the same manner whereby the node at fault can be viewed in the same way as above On an IMS graphics terminal identifying which node number corresponds to which panel is achieved by acce...

Страница 33: ...ase Pg 13 Open Circuit Monitored circuit broken Pg 10 Short Circuit Monitored circuit or 24 volt supply shorted Pg 11 Node Missing Communication lost with specified panel Degraded Style 7 The specifie...

Страница 34: ...cuit and will display a Degraded Style 7 fault 3 3 4 Network Initialization Incomplete During the network boot up sequence there are panel s that have not successfully initialized May require a full n...

Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...

Страница 36: ...U Remote Zone Display Unit that has an off normal condition including those which do not cause System Fault 4 1 2 Operating Sequence For both networked and non networked systems from the base display...

Страница 37: ...uts and alarms continues 6 LED display board fault There is a fault with a zone or relay LED display board This can occur if the wrong number of display boards is installed 7 LCD display fault A fault...

Страница 38: ...Stack error The execution stack in the RAM has overflowed or under flowed Link error An invalid value has been found in a link field in an equation Invalid MAF output This indicates a conflict in info...

Страница 39: ...ntroller time date clock registers has failed The Controller will restart and try the test again 24 Clock chip RAM write read fail A test of the Controller s clock RAM has failed The Controller will r...

Страница 40: ...y FF Firefighter Facility part of Display Keyboard FIP Fire Indicator Panel FRC Flat Ribbon Cable I O Input Output LCD Liquid Crystal Display LED Light Emitting Diode MAF Master Alarm Facility Max Max...

Страница 41: ...V1 Programmable Variable Number 1 VA Volts Amperes VB Battery Backed Voltage VNB Non Battery Backed Voltage VBF Fused Battery Backed Voltage VNBF Fused Non Battery Backed Voltage WS Warning System Z1...

Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...

Страница 43: ...itch to Isolate position 2 Press and hold the BGM PAGING key for 2 seconds until PROGRAM LED only is on 3 Press BGM PAGING key successfully until LAMP TEST is flashing The Fault memory will be display...

Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...

Страница 45: ...l is swapping identical components over and testing to see if the fault follows the device This allows you to eliminate if the fault is located on a device card within the panel or out in the field wi...

Страница 46: ...djust the power output NOTE However in terms of efficiency and battery capacity that it is preferable to reduce the volume by adjusting the speaker taps to a lower setting and leaving the controls tur...

Страница 47: ...teady This feature is designed to assist in determining if an Audio fault indication on the ECP is was an amplifier fault speaker line fault or a strobe line fault To extinguish the steady red LED swi...

Страница 48: ...lytic capacitors in some strobe lights which can weld the relay contacts It is also recommended that you don t use cables shorter than 100m or if you do then add resistor s to make enough total resist...

Страница 49: ...ndicated a more detailed description of settings included in Table 4 Switches SW1 4 determine the address 0 15 of the module and thus the output line numbers as seen in Table 3 The mapping of the evac...

Страница 50: ...gnal for EVACUATE 5 4 4 STBM9008 Board Installation To install the STBM9008 Module perform the following steps STEP 1 Install the STBM9008 board into the DIN rail housing and install the unit on the D...

Страница 51: ...the positive input Please see Termination Points and Example Wiring figure shown below Inputs that are programmed as General Purpose GP inputs do not need the zener diode end of line Cables should hav...

Страница 52: ...will indicate a WIP Line fault associated with that Zone A WIPS Module Fault may be present if one or more WIP Line Fault LEDs are active The zones in fault will indicate will indicate which WIP Modu...

Страница 53: ...to the respective Fault on the ECP System Fault Display NOTE Any WIPS Module Failure or WIP Speech cable fault will activate WIP SYSTEM FAULT LED on the ECP System Fault Display The LED will flash whi...

Страница 54: ...P MECP failure will be present on any SECP when a WIP Line fault or WIPS Module failure is detected on the MECP In a similar fashion any WIP SECP failure will be present on any SECP when a WIP Line fa...

Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...

Страница 56: ...whether this is the case turn off the power and remove the amplifier card that is generating the fault Remove links 10 and 11 on any amplifier type to disable amplifier monitoring If the faults can be...

Страница 57: ...lack of earthing that should be earthed can contribute see PBQ0080 LT0088 Fig 16 4 PBQ0080 Servicing When powered up the Alert Evac and PA Indicators for Zone 2 were found to be flashing together Wha...

Страница 58: ...n Simplex T3 Strobes not functioning Simplex T3 strobes only work on EVAC 1 The Positive should be wired to Terminal B and the Negative should be wired to Terminal A 2 Dip switch setting 5 6 7 8 have...

Страница 59: ...Page 59 of 60 6 0 National Contact Directory...

Страница 60: ...Office Sydney Unit 4 2 8 South Street RYDALMERE NSW 2116 Phone 02 9638 8280 Fax 02 9638 8285 Melbourne 47 Gilby Road NOTTING HILL VIC 3149 Phone 03 9538 7250 Fax 03 9538 7200 Freecall 1300 552 559 Bri...

Отзывы: