Devices are supplied with DIPSWITCH set to 255
DIPSWITCHES are labeled 1 to 8 (left to right)
Switch 1 = 1
Switch 2 = 2
Switch 3 = 4
Switch 5 = 8
Switch 6 = 16
Switch 7 = 32
Switch 8 = 128
Turn Switch ON to add the above number to the address. Examples:
Address 10 = Switch 2 & 5 ON all others OFF
Address 105 = Switch 1, 4, 6 & 7 ON others OFF
The highest IDNet device address is 250.
The highest MAPNet device address is 127.
1.1.3.1.10 End of Line Resistors
For a comprehensive pocket reference guide contact your local Simplex® branch
4090-9001
Supervised IAM
Current Limited
6.8kΩ
4.7kΩ & 1.8kΩ
4090-9101
Monitor ZAM
3.3kΩ
4090-9118
Relay IAM with T-Sense
Current Limited
6.8kΩ
4.7kΩ & 1.8kΩ
4090-9120AU
6 Pt I/O Module
Current Limited
6.8kΩ
4.7kΩ & 1.8kΩ
2190-9156
Mapnet Monitor ZAM
3.3kΩ
2190-9164
Mapnet Signal ZAM
10kΩ
4100 EWIS
WIPs
10kΩ
4100 8pt Monitor Card
Conventional Zone Card
3.3kΩ
4100 6 Signal Card
Signal Card
10kΩ
4100 24-pt IO Card
Pluggable Resistors on card 2.2kΩ Input
20Ω Output
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...