1.1.3.1.5 Extra Device
Description:
The panel has identified a device at an address that is not in the panel programming.
NOTES
:
Only one extra device per loop is ever displayed. Fixing one extra device may display a new
extra device fault (if present)
Extra Device Faults take a longer time to appear and clear than other faults.
Possible causes:
Device not added to the program
Device addressed incorrectly
Device not programmed at all (IDNet address 255, MAPNet address 0)
Suggested solutions:
1< Device > 255
Device = 255 or 0
The device has
not been
addressed.
Scroll to the NEXT event.
Channel = Loop Number
DEVICE = Address
Scroll through the Historical
Fault Log for the following
message
“MAPNET EXTRA DEVICE”
Check Program has a
device at that address
Check and fix “NO ANSWER” Device
faults as this may clear extra device
faults
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...