4
The 4100U/4100ES BMUX Comms Module,
Continued
Requirements
and Limitations
The BMUX Comms Module can communicate with up to 63 2120 transponders or DC Loop
peripheral devices. See Table 2 for the General System Specifications.
Table 2: General System Specifications
Electrical Specifications
Module Input Voltage
24 VDC from FACP
Current Consumption
220 mA max with fully loaded channel
Wiring Sizes
18 AWG (0.82 mm
2
) minimum to 12 AWG (3.31 mm
2
) max-
imum
Maximum Number of BMUX
Comms Modules per system
2
Environmental Specifications
Operating Temperature
32
°
to 120
°
F (0
°
to 49
°
C)
Humidity
Up to 93% relative humidity at 90
°
F (32
°
C)